Commissioning – Lenze SMD 0-37kW-22kW Full I/O User Manual
Page 25
Lenze 13466183 EDBSC03 v7
25
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Lenze
Selection
TPDO#2 configuration parameters
h90
(1)
TPDO#2 COB ID
641 0 2047 If h53 = 0, 2: Setting will change to
640 + Node ID during power-up or h58
reset.
h91
(1)
TPDO#2 enable/
disable
0
0 Disable
1 Enable (no RTR)
2 Enable (with RTR)
Enable individual polling of TPDO#2
h92 TPDO#2
transmission type
255 0 255
•
h92 = 0...240: Transmit TPDO#2 after
every n
th
SYNC received + Event + RTR
(if enabled)
•
h92 = 253: Event + RTR (if enabled)
•
h92 = 254: COS triggered (WORD0 of
TPDO#2) + Event + RTR (if enabled)
•
h92 = 255: Event + RTR (if enabled)
h93
(1)
TPDO#2 inhibit time
50
0
{0.1 ms}
65535 Sets minimum time between TPDO#2
transmissions (h93 = 50 = 5.0 ms)
h94 TPDO#2 event timer
0
0
{ms}
65535
•
Sets the fixed interval for TPDO#2
transmission
•
h94 = 0: disables event timer
h96
(1)
TPDO#2 mapping
(see TPDO mapping
details)
0
0 C0150 + C50 signed
C50 scaling: + 50 = + 1.0 Hz
1 C0150 + C50 unsigned
C50 scaling: 10 = 1.0 Hz
2 Controller status in C0135 format +
frequency setpoint signed
Can be used to control other controllers
(see example in section 4.5)
3 Controller status in C0135 format +
frequency setpoint unsigned
4 402 Device profile: Statusword
0x6041
5 402 Device profile: Statusword
0x6041 + vl control effort 0x6044
•
vl control effort units = signed RPM
•
RPM calculation based on C87 and C89
6 C0150 + C50 signed and scaled +
digital input + analog input
C50 scaling: +/- 16384 = C11
h97 TPDO#2 WORD0
bit mask
65535
0
65535
•
COS (change of state) bit mask applied
to WORD0 of TPDO selected by h96.
•
h97 = 65535: activates all bits of
WORD0 for COS triggering
•
h97 = 0: disables COS triggering
h99 TPDO#2 status
0 255
•
Read-only
•
Number of transmitted TPDO#2
messages
•
Above 255, starts over at 0
n20 Power up state
0
0 Quick stop
Selects controller power up state when
C01 = 3 (CANopen control)
1 Inhibit
(1)
These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”