Commissioning, 3 parameter menu – Lenze SMD 0-37kW-22kW Full I/O User Manual
Page 15
![background image](/manuals/565697/15/background.png)
Lenze 13466183 EDBSC03 v7
15
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Lenze
Selection
C00 Password entry
0
0 999 Visible only when password is active
(see C94)
C01 Setpoint and control
source
0
Setpoint source:
Control configuration:
0 Analog input (terminal 8; see C34)
Control = terminals
Programming = keypad/limited CANopen
Monitoring = CANopen
Note:
RPDOs not processed in these
modes
1 Code c40
2 CANopen
Control = terminals
Programming = CANopen/keypad
Monitoring = CANopen
Note:
Only frequency setpoint part of
RPDOs are processed in this mode
3 CANopen
Control = CANopen
Programming = CANopen/keypad
Monitoring = CANopen
C02 Load Lenze setting
0 No action/loading complete
• C02 = 1...4 only possible with
OFF or 1nh
• C02 = 2 : C11, C15 = 60 Hz
1 Load 50 Hz Lenze settings
2 Load 60 Hz Lenze settings
3 Load OEM settings (if present)
4 Translate
WARNING!
C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes
CE1...CE3.
NOTE
If an EPM that contains compatible data from a previous software version is
installed, C02 = 4 converts the data to the current version.
4.3
Parameter Menu