Commissioning – Lenze SMD 0-37kW-22kW Full I/O User Manual

Page 20

background image

20

Lenze 13466183 EDBSC03 v7

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

CANopen / System bus parameters

h42 Guard time

0

0

{ms}

65535

h42 x h43 = node life time

If RTR frame with ID = 0x700 + Node ID

(h50) is not received during the node life

time, the controller will react according

to h44

If heart beat message is enabled, the

guard function is disabled

h44 is only active when C01 = 3 and

h42 x h43 > 0

h43 Life time factor

0

0 255

h44 Guard time event

reaction

0

0 Not active
1 Inhibit
2 Quick stop
3 Trip fault FC3

h45 Error behavior

1

0 Transition to pre-operational (only if

current state is operational)

Specifies action taken by the drive when it

encounters a communication error

(ex. Node guarding event or Bus Off)

1 No state change
2 Transition to stopped

h46 Message monitoring

time

0

0

{ms}

65535

h46 and h47 can be used to monitor

all valid messages (e.g. SDO, SYNC,

PDO...)

h46 = 0 or h47 = 0 disables message

monitoring function

h47 is only active when C01 = 3

h47 Message monitoring

time out reaction

0

0 Not active
1 Inhibit
2 Quick stop
3 Trip fault FC3

h48 Monitoring timeout

status

Bits:

• Read-only

• Indicates cause of FC3 fault, inhibit, or

quick stop (depending on the settings of

h44, h47, h65, h75)

0 Guard time timeout
1 No valid message received
2 RPD01 timeout
3 RPD02 timeout
4 CAN initialization fault
5 reserved

Bits 5…7 create a binary number from 0 to

7 indicating the number of overflows in the

receive buffers (h49 bits 6 and 7)

6 reserved
7 reserved

h49 CAN controller

status value (8-bit

value)

0 Receive/transmit error warning flag

(96 or more errors)

• Read-only

• CAN warnings and errors

1 Receive error warning flag (96 or

more receive errors)

2 Transmit error warning flag (96 or

more transmit errors)

3 Receive error passive flag (128 or

more receive errors)

4 Transmit error passive flag (128 or

more transmit errors)

5 Bus-off error flag
6 Receive buffer 0 overflow flag
7 Receive buffer 1 overflow flag

h50

(1)

CAN address

(Node ID)

1

1 127 If h53 = 0, 1: maximum setting = 63