beautypg.com

Warning – Bryant Series E/F 310AAV User Manual

Page 8

background image

8

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury or death.
The operation of exhaust fans, kitchen ventilation fans,

clothes dryers, attic exhaust fans or fireplaces could create a

NEGATIVE PRESSURE CONDITION at the furnace.

Make--up air MUST be provided for the ventilation devices,

in addition to that required by the furnace. Refer to Carbon

Monoxide Poisoning Hazard warning in venting section of

these instructions to determine if an adequate amount of

make--up air is available.

!

WARNING

The requirements for combustion and ventilation air depend

upon whether or not the furnace is located in a space having a

volume of at least 50 cu/ft. per 1,000 Btuh input rating for all gas
appliances installed in the space.

S

Spaces having less than 50 cu/ft. per 1,000 Btuh re-
quire the OUTDOOR COMBUSTION AIR
METHOD.

S

Spaces having at least 50 cu/ft. per 1,000 Btuh may use
the INDOOR COMBUSTION AIR, STANDARD or
KNOWN AIR INFILTRATION METHOD.

Outdoor Combustion Air Method

1. Provide the space with sufficient air for proper combus-

tion, ventilation, and dilution of flue gases using perman-

ent horizontal or vertical duct(s) or opening(s) directly
communicating with the outdoors or spaces that freely

communicate with the outdoors.

2. Fig. 7 illustrates how to provide TWO OUTDOOR

OPENINGS, one inlet and one outlet combustion and

ventilation air opening, to the outdoors.

e. One opening MUST commence within 12 in. (300

mm) of the ceiling and the second opening MUST
commence within 12 in. (300 mm) of the floor.

f. Size openings and ducts per Fig. 7 and Table 2.

g. TWO HORIZONTAL DUCTS require 1 sq./in. of free

area per 2,000 Btuh (1,100 mm

2

/kW) of combined

input for all gas appliances in the space per Fig. 7 and
Table 2.

h. TWO OPENINGS OR VERTICAL DUCTS require 1

sq./in. of free area per 4,000 Btuh (550 mm

2

/kW) for

combined input of all gas appliances in the space per
Fig. 7 and Table 2.

3. ONE OUTDOOR OPENING requires:

a. 1 square inch of free area per 3,000 Btuh (734

mm2/kW) for combined input of all gas appliances in

the space per Table 2 and

b. Not less than the sum of the areas of all vent connect-

ors in the space.

The opening shall commence within 12 in. (300 mm) of the
ceiling. Appliances in the space shall have clearances of at least 1

in. (25 mm) from the sides and back and 6 in. (150 mm) from the

front. The opening shall directly communicate with the outdoors
or shall communicate through a vertical or horizontal duct to the

outdoors or spaces (crawl or attic) that freely communicate with
the outdoors.
Indoor Combustion Air NFPA & AGA
Standard and Known--Air--Infiltration Rate Methods
Indoor air is permitted for combustion, ventilation, and dilution,

if the Standard or Known--Air--Infiltration Method is used.

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in death and/or

personal injury.
Many homes require air to be supplied from outdoors for

furnace combustion, ventilation, and dilution of flue gases.

The furnace combustion air supply must be provided in

accordance with this instruction manual.

!

WARNING

Table 2—Minimum Free Area Required for Each Combustion Air Opening of Duct to Outdoors

FURNACE

INPUT

(BTUH)

TWO HORIZONTAL DUCTS

SINGLE DUCT OR OPENING

TWO OPENINGS OR VERTICAL

DUCTS

(1 SQ. IN./2,000 BTUH)

(1,100 SQ. MM/KW)

(1 SQ. IN./3,000 BTUH)

(734 SQ. MM/KW)

(1 SQ. IN./4,000 BTUH)

(550 SQ. MM/KW)

Free Area of Open-

ing and Duct

Sq. In. (Sq. mm)

Round Duct

Dia.

In. (mm)

Free Area of Open-

ing and Duct

Sq. In. (Sq. mm)

Round Duct

Dia.

In. (mm)

Free Area of Open-

ing and Duct

Sq. In. (Sq. mm)

Round Duct

Dia.

In. (mm)

44,000

22 (14194)

6 (152)

14.7 (9484)

5 (127)

11 (7096)

4 (102)

66,000

33 (21290)

7 (178)

22.0 (14193)

6 (152)

16.5 (10645)

5 (127)

88,000

44 (28387)

8 (203)

29.3 (18903)

7 (178)

22 (14193)

6 (152)

110,000

55 (35484)

9 (229)

36.7 (23677)

7 (178)

27.5 (17742)

6 (152)

132,000

66 (42580)

10 (254)

44 .0 (28387)

8 (203)

33 (21290)

7 (178)

154,000

77 (49677)

10 (254)

51.3 (33096)

9 (229)

38.5 (24839)

8 (203)

EXAMPLES: Determining Free Area

FURNACE

WATER HEATER

TOTAL INPUT

110,000

+

30,000

=

(140,000 divided by 4,000)

=

35.0 Sq. In. for each two Vertical Ducts or Openings

66,000

+

40,000

=

(106,000 divided by 3,000)

=

35.3 Sq. In. for a Single Duct or Opening

88,000

+

30,000

=

(118,000 divided by 2,000)

=

59.0 Sq. In. for each of two Horizontal Ducts

310AA

V