Table 8—Exterior Masonry Chimney Fan + Nat Installations
with Type--B Double Wall Vent Connectors ENFPA & AGA
Combined Appliance Maximum Input
Rating in Thousands of Btuh per Hour
VENT HEIGHT
FT. (M)
INTERNAL AREA OF CHIMNEY
SQ. IN. (SQ. MM)
12
(7741)
19
(12258)
28
(18064)
38
(24516)
6 (1.8)
74
119
178
257
8 (2.4)
80
130
193
279
10 (3.0)
84
138
207
299
15 (4.5)
NR
152
233
334
20 (6.0)
NR
NR
250
368
30 (9.1)
NR
NR
NR
404
Table 9—Minimum Allowable Input Rating of Space--Heat-
ing Appliance in Thousands of Btuh per Hour
VENT HEIGHT
FT. (M)
INTERNAL AREA OF CHIMNEY
SQ. IN. (SQ. MM)
12
(7741)
19
(12258)
28
18064)
38
(24516)
Local 99% Winter Design Temperature: 17 to 26 degrees F
6
0
55
99
141
8
52
74
111
154
10
NR
90
125
169
15
NR
NR
167
212
20
NR
NR
212
258
30
NR
NR
NR
362
Local 99% Winter Design Temperature: 5 to 16 degrees F*
6
NR
78
121
166
8
NR
94
135
182
10
NR
111
149
198
15
NR
NR
193
247
20
NR
NR
NR
293
30
NR
NR
NR
377
Local 99% Winter Design Temperature: ---10 to 4 degrees F*
6
NR
NR
145
196
8
NR
NR
159
213
10
NR
NR
175
231
15
NR
NR
NR
283
20
NR
NR
NR
333
30
NR
NR
NR
NR
Local 99% Winter Design Temperature: ---11
_
F (16_C)
or
lower
Not recommended for any vent configuration.
*The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE
Fundamentals Handbook, Climatic Design Information chapter, Table 1A
(United States) or the 2005 ASHRAE Fundamentals handbook, Climatic
Design Information chapter, and the CD---ROM included with the 2005
ASHRAE Fundamentals Handbook.