beautypg.com

Warning – Bryant Series E/F 310AAV User Manual

Page 24

background image

24

24--V WIRING
Make field 24--v connections at the 24--v terminal strip. (See Fig.

25.) Connect terminal Y as shown in Fig. 26 for proper cooling
operation. Use only AWG No. 18, color--coded, copper

thermostat wire.
The 24--v circuit contains an automotive--type, 3--amp. fuse

located on the control. Any direct shorts during installation,

service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3--amp. fuse of identical

size.
ACCESSORIES

1. Electronic Air Cleaner (EAC)

Connect an accessory Electronic Air Cleaner (if used) us-

ing 1/4--in female quick connect terminals to the two male
1/4--in quick--connect terminals on the control board
marked EAC--1 and EAC--2. The terminals are rated for

115 VAC, 1.0 amps maximum and are energized during
blower motor operation. (See Fig. 24.)

2. Humidifier (HUM)

Connect an accessory 24 VAC, 0.5 amp. maximum hu-
midifier (if used) to the 1/4--in male quick--connect HUM

terminal and COM--24V screw terminal on the control
board thermostat strip. The HUM terminal is energized

when gas valve relay (GVR) is energized. (See Fig. 24.)

NOTE: A field--supplied, 115--v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
NOTE: DO NOT connect furnace control HUM terminal to
HUM (humidifier) terminal on Thermidistatt, Zone Controller
or similar device. See Thermidistatt, Zone Controller,
thermostat, or controller manufacturer’s instructions for proper
connection.
VENTING
The furnace shall be connected to a listed factory built chimney

or vent, or a clay--tile lined masonry or concrete chimney. Venting
into an unlined masonry chimney or concrete chimney is

prohibited.
When an existing Category I furnace is removed or replaced, the

original venting system may no longer be sized to properly vent

the attached appliances. An improperly sized Category I venting
system could cause the formation of condensate in the furnace

and vent, leakage of condensate and combustion products, and
spillage of combustion products into the living space.
Vent system or vent connectors may need to be resized. Vent

systems or vent connectors, must be sized to approach minimum
size as determined using appropriate table found in the NFGC.
GENERAL VENTING REQUIREMENTS
Follow all safety codes for proper vent sizing and installation

requirements, including local building codes, the National Fuel
Gas Code ANSI Z223.1--2009/NFPA 54--2009 (NFGC), Parts 12

and 13, local building codes, and furnace and vent manufacturers’
instructions.

CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each

appliance connected to the venting system being placed into

operation could result in carbon monoxide poisoning or

death.
The following steps shall be followed for each appliance

connected to the venting system being placed into

operation, while all other appliances connected to the

venting system are not in operation:

1. Seal any unused openings in venting system.

2. Inspect the venting system for proper size and horizontal

pitch, as required in the National Fuel Gas Code, ANSI

Z223.1/NFPA 54 and these instructions. Determine that

there is no blockage or restriction, leakage, corrosion and

other deficiencies, which could cause an unsafe condition.

3. As far as practical, close all building doors and windows

and all doors between the space in which the appliance(s)

connected to the venting system are located and other

spaces of the building.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected

to the venting system. Turn on any exhaust fans, such as

range hoods and bathroom exhausts, so they are operating

at maximum speed. Do not operate a summer exhaust fan.

6. Follow the lighting instructions. Place the appliance

being inspected into operation. Adjust the thermostat so

appliance is operating continuously.

7. Test for spillage from draft hood equipped appliances at

the draft hood relief opening after 5 minutes of main burner

operation. Use the flame of a match or candle.

8. If improper venting is observed during any of the above

tests, the venting system must be corrected in accordance

with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 .

9. After it has been determined that each appliance

connected to the venting system properly vents when tested

as outlined above, return doors, windows, exhaust fans,

fireplace dampers and any other gas--fired burning

appliance to their previous conditions of use.

!

WARNING

These furnaces are design--certified as Category I furnaces in

accordance with ANSI Z21.47--2009/CSA 2.3--2009 and operate

with a non--positive vent static pressure to minimize the potential
for vent gas leakage. Category I furnaces operate with a flue loss

not less than 17 percent to minimize the potential for
condensation in the venting system. These furnaces are approved

for common venting and multistory venting with other fan

assisted or draft hood equipped appliances in accordance with the
NFGC, the local building codes, and furnace and vent

manufacturers’ instructions.
The following information and warning must be considered in

addition to the requirements defined in the NFGC.

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury or death.
Do not bypass the draft safeguard switch, as an unsafe

condition could exist which must be corrected.

!

WARNING

310AA

V