310aa v, Fig. 49 --- troubleshooting guide – Bryant Series E/F 310AAV User Manual

Page 49

background image

49

Is LED status light on?

Is LED status light b

linking r

apidly without a

pause?

Is LED status light b

linking ON/OFF slo

wly

with a combination of shor

t and long flashes?

Deter

mine status code

.

The status code is a

2 digit n

umber with the first digit deter

mined

by

the n

umber of shor

t flashes and the second

digit b

y the n

umber of long flashes?

Go to section belo

w f

or the status code that

w

as flashed.

Is there 115V at L1 and L2?

Is there 24V at SEC-1 and SEC-2?

Replace fur

nace control.

Chec

k f

or correct line v

oltage polar

ity

. If units

are twinned, chec

k f

or proper lo

w-v

oltage

(24V) tr

ansf

or

mer phasing.

To

recall status code br

iefly remo

ve

and reconnect one RED wire from the dr

aft

saf

eguard s

witch to displa

y stored status code

. On RED LED control do not

remo

ve

po

w

er or b

lo

w

er access panel bef

ore initiating status code recall.

Y

ou

can also recall the pre

vious status code b

y momentar

ily shor

ting the

TEST/TWIN

ter

minal to Com24V ter

minal until the LED goes out.

LED will flash the status

code of the pre

vious f

ault or status code #11 (1 shor

t and 1 long flash) if there

w

as no pre

vious f

ault.

After the control repeats the code 4 times

, the control

will go through a br

ief component test sequence

.

The inducer will star

t and r

un

for the entire component test.

The HSI, b

lo

w

er motor F

AN speed (AMBER LED

boards only) HEA

T speed, and COOL speed will r

un f

or 10 – 15 seconds each.

Gas v

alv

e and humidifier will not be tur

ned on.

W

as there a pre

vious status code

other than #11?

Is door s

witch closed?

Is there 115V going to s

witch?

Replace door s

witch.

Replace tr

ansf

or

mer

.

Does the control respond to

W

, Y1 (if present),

Y/Y2, and G (24V) ther

mostat signals?

Run system through a heating or cooling cycle to chec

k oper

ation.

Status codes are er

ased

after 72 hours

. On RED LED boards stored

status codes can also be er

ased whene

ve

r

(115V or 24V) is interr

upted.

Replace fur

nace control.

Is door s

witch closed?

Is circuit break

er closed?

Chec

k f

or contin

uity in wire from circuit break

er

to fur

nace

.

Close circuit break

er and go bac

k to ST

AR

T.

Chec

k room ther

mostat or

interconnecting cab

le

.

Is 24V present at

W

, Y1 (if present),

Y/Y2 or

G ther

mostat ter

minals on the fur

nace control?

Disconnect all the ther

mostat wires from the

fur

nace control.

Does the prob

lem repeat when using

a jumper wire?

The ther

mostat is not compatib

le with the

fur

nace control.

Either install a ballast resistor

,

connect the Com24V ther

mostat ter

minal to

the ther

mostat, or replace the ther

mostat.

NO

YES

YES

NO

NO

YES

YES

YES

YES

NO

YES

YES

NO

YES

NO

YES

NO

NO

NO

YES

NO

YES

NO

ST

AR

T

NO

A02106a

Fig. 49

--- Troubleshooting Guide

310AA