Bryant Series E/F 310AAV User Manual

Page 29

background image

29

Table 10—Minimum Vent Heights

Caution!! for the following applications, use the minimum vertical vent heights as specified below.

For all other applications, follow exclusively the national fuel gas code.

FURNACE

ORIENTATION

VENT

ORIENTATION

FURNACE

INPUT (BTUH/HR)

MINIMUM VENT

DIAMETER

IN. (mm)*

MINIMUM VERTICAL VENT

HEIGHT

FT. (M)**

Downflow

Vent elbow left, then

up Fig. 32

154,000

132,000

110,000(036/---12 only)

5 (127)

12 (3.6)

Horizontal Left

Vent elbow right,

then up Fig. 35

154,000
132,000

5 (127)

7 (.65)

Horizontal Left

Vent Elbow up

Fig.

36

154,000

132,000

5 (127)

7 (,65)

Horizontal Left

Vent elbow right

Fig. 37

154,000

5 (127)

7 (.65)

Downflow

Vent elbow up then

left Fig. 30

110,000

(036/---12 only)

5 (127)

10 (3.0)

Downflow

Vent elbow up, then

right Fig.

33

110,000

(036/---12 only)

5 (127)

10 (3.0)

* 4 in. (102 mm) inside casing or vent guard

** Including 4 in. (102 mm) vent section (s)

NOTE: All vent configurations must also meet National Fuel Gas Code (NFGC) venting requirements

NOTE: For all unlisted vent configurations, refer to National Fuel Gas Code (NFGC) venting requirements.

SEE NOTES: 1,2,4,7,8,9

on the page following

these figures

A03208

Fig. 28

--- Upflow Application--Vent Elbow Up

SEE NOTES: 1,2,3,4,7,8,9

on the pages following

these figures

A03209

Fig. 29

--- Upflow Application--Vent Elbow Right

310AA

V