6 technical data – JUMO 709050 IPC IGBT Power Converter IPC 70A Operating Manual User Manual
Page 40

6 Technical data
40
[IGBT Power Converter 70A] 02.08
Power loss P
tot
(W)
Power loss occurs in the form of thermal discharge at the cooling body of the
power converter, at the EMC filter and choke.
v Chapter 3.3 „Umgebungsbedingungen“
Control accuracy
The regulation will eliminate supply voltage variations within the tolerances
range (+15%/-20%) with an accuracy of
Ϯ
0.5
%
Electrical
connection
Control leads via plug-in screw terminals for conductor cross sections
0.5 … 2.5mm
2
In the power section via cable lugs.
protection rating
IP00 as per EN 60 529, the cooling body is connected to PE
Protection class
Protection class I, with isolated control circuitry for connection to SELV circuits
Permissible ambient
temperature range
5 … 40°C (3K3 as per EN 60721-3-3)
Permissible storage
temperature range
-10 … +70°C (1K3 as per EN 60 721-3-1)
Cooling
forced convection, maximum inlet air temperature 35°C
Climatic conditions
Rel. humidity
≤ 5 to 85 % annual average, no condensation
3K3 as per EN 60721
Installation position
vertical
Operating conditions
The converter is designed as a built-in device as per EN 50178
Pollution degree 2, overvoltage category Ü III
Test voltage
as per EN 50178
Creepage distances
Control section to load circuit
≥ 5.5 mm
Control section to housing
≥ 5.5 mm
The converter can be connected to SELV circuits.
SELV = Separate Extra Low Voltage (safe low voltage)
Housing
Metal housing
Weight
approx. 9 kgs