5 Settings
36
[IGBT Power Converter 70A] 02.08
Alternative
setting option:
To simulate a load fail, adjust the „load fail adjust“ trimmer such that the yellow
„load fail“ LED lights up.
5.12.2 Safety cut-out in the power section
A safety cut-out occurs in the event of a defect in the choke or in the
semiconductor power module; the output voltage between terminals D and 1D
is switched off.
This state is indicated by the „load fail“ LED, and the fault signal relay drops
out.
This safety cut-out remains activated even when the fault has been remedied.
It can only be reset by disconnecting the voltage supply.
h Switch the device off briefly, and then on again
If in the event of a fault the semiconductor module goes low-resistance, it is
possible to produce the full voltage supply of the power section for the
consumer (load).
To safely disconnect the resulting overload and to protect the load, provide a
cut-out in the supply cable in the form of a CMC (Q) automatic cut-out or a
semiconductor fuse in addition to the protection circuit-breaker. An automatic
cut-out combining both functions can be used in the power section to cut out
the voltage supply.
H
The smallest change in resistance that can be detected is 5 % of the
nominal load resistance.
A
However, terminals D and 1D may still carry dangerous voltage from
the supply. They are not electrically isolated from the supply!