11 setting the current limit (max. current adjust), Setting the current limit (max. current adjust), Adjust) – JUMO 709050 IPC IGBT Power Converter IPC 70A Operating Manual User Manual
Page 34: Load fail adjust), 5 settings

5 Settings
34
[IGBT Power Converter 70A] 02.08
5.11 Setting the current limit (max. current adjust)
h The front „max. current adjust“ trimmer can be used to limit the rms value
of the load current over a range of 10 to 100% of the rated converter
current.
1.5 clockwise turns correspond to increasing the response threshold by
approx. 10% of the rated converter current.
Correct
measurement
The red „current limit“ LED is on when current limiting is active.
Factory setting
The trimmer is set to the maximum rated current.
5.12 Total and partial load failure monitoring (load fail adjust)
If the load resistance changes during operation, this will be detected by the
partial load monitoring and indicated through the signal output.
The response threshold can be adjusted by the „load fail adjust“ trimmer on
the front panel (load fail adjust) between 20 and 100% of the rated converter
current.
Factory setting
The trimmer is set to approx. 20 %.
The signal output provided is a floating contact or an optocoupler, depending
on the extra (type) code.
Action
Response
Turn the „max. current
adjust“ trimmer clockwise
The current limit will increase
Turn the „max. current
adjust“ trimmer counter-
clockwise
The current limit will reduce
A
A true-rms meter must be used for measuring voltage, power or
current, because the load current is pulsating DC.
A meter calibrated for alternating current (AC) and sinusoidal
waveforms will produce false readings!
H
The smallest change in resistance that can be detected is 5 % of
the nominal load resistance.