Operating procedures

20



Setting the Tn (resetting time)

1.

Press the key

.

The indicator light blinks and the effective value for Tn
appears on the MULTI-DISPLAY (LED).

2.

Follow the instructions

3.

for

4.

(example: 1200 s).



Setting range for Tn: 1 to 9998 s.
With Tn set to 9999, the integral part of the controller is
deactivated (use of a P or PD type controller).





Setting the Tv (lead time)

1.

Press the key

.

The indicator light blinks and the effective value for Tv
appears on the MULTI-DISPLAY (LED).

2.

Follow the instructions

3.

for

4.

(example: 120 s).





Setting range for Tv: 0 to 1000 s.
With Tv set to 0 eingestellt, the differential part of the
controller is deactivated (use of a P or PI type controller).