beautypg.com

JULABO LC 4 Temperature controller User Manual

Page 19

background image

LC4

19

5.7. Setting the temperatures


Setting the working temperature:

1.

Press the setpoint key

.

The indicator light blinks and the effective value appears
on the MULTI-DISPLAY (LED).

2.

Use the cursor keys

to move left or right on the

display until the numeral you wish to change is blinking.

3.

Use the increase/decrease arrows

to change the

selected numeral (-, 0, 1, 2, 3, ... 9).

4.

Press enter

to store the selected value (example: 37.0

°C).

The working temperature is maintained constant after a short
heat-up time (example: 37.0 °C).


5.8. Setting the PID control parameters Xp, Tn and Tv





Setting the Xp (proportional range)

1.

Press the key

.

The indicator light blinks and the effective Xp value
appears on the MULTI-DISPLAY (LED).

2.

Use the cursor keys

to move left or right on the

display until the numeral you wish to change is blinking.

3.

Use the increase/decrease arrows

to change

the selected numeral (-, 0, 1, 2, 3, ... 9).

4.

Press enter

to store the selected value (example: 12

°C).


Setting range for the Xp parameter: 0.1 to 50 °C