ERICO ER Series 4m Stainless Steel Cantilevered Mast User Manual
Detail "a
3.3FT [1M]
Mast Detail
2 Holes, 0.43 [10.9mm]
1.57 [39.9mm]
3.54 [89.9mm]
4.72 [119.9mm]
Not to Scale
Typical ALOF1GS Wall Bracket Base
2
-
Note: This is one of several alternative installation methods.
Refer to ERICO installation handbook for more details.
Typical LPC126R Cable Strap
(ERICO Part # A930W004) Drive-in Type Anchor
(ERICO Part # LPC126R) Copper Cable
(ERICO Part # LPC805) Copper Strap
Not to Scale
Mast Adapter
(ERICO Part # INTCPTSIIER2)
Stainless Steel Mast
(ERICO Part # ER22000SS)
Bonding Clamp
(ERICO Part # LPC570)
Stainless Steel Cable Tie
(ERICO Part # CABTIESS)
Three every 3.3FT [1M]
Mast Support Bracket
(ERICO Part # ALOF1GS)
For complete
grounding system
refer to Detail "A"
Two downconductors
are required
Lightning Event Counter
Refer to installation manual
for alternate locations
(ERICO Part # LECIV)
SI INTERCEPTOR
(ERICO Part # SI25i, SI40i or SI60i)
Suggested triangular grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench
20FT [6.1M] in length and approximately 2.5FT [0.8M] deep. 20FT [6.1M] of 2/0 conductor is laid in the
trench and is connected to the ground rod using "GY" CADWELD connection. The conductor in
each trench is encased in ERICO GEM material. Ground rods must extend 10FT [3M] below ground
level.
®
2/0 Conductor
(3 x 20FT [6.1M] length)
Enclosed in
ERICO GEM material
Bond to the existing
building ground system
Detail "A"
Lightning Event Counter
(ERICO Part # LECIV)
ERICO CADWELD "GR" Connection
or mechanical connection
(ERICO Part # LPC790)
Downconductor
(ERICO Part # LPC126R)
Ground Inspection Well
Minimum 5/8" X 8' [16mm X 2.4M] long
ground rod in three locations
LPC570 Bronze Pipe Bonding Clamp
Installing contractor to field
adjust and insure a secure bond
on highest ER series mast
LPC126R Copper Cable
®
Not to Scale
1
-
End View
®
®
-
2
1
-
3
-
-
2
1
-
3
-
Stainless Steel Mast
(ERICO Part # ER32000SS)
ER32000SS
ER22000SS
INTCPTSIIER2
3
-
3.3FT [1M]
TECHNICAL SUPPORT
www.erico.com
IP79107_B
1 OF 1
INSTRUCTION SHEET
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com and from your ERICO customer service representative.
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be completely followed to ensure proper and safe installation and performance.
3.
Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and death.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
ERICO INTERCEPTOR SI25i, SI40i or SI60i
Installation Instructions for 4m Stainless Steel Cantilevered Mast - ER Series
Terminal Elevation: 3m Above Structure
© 2006, 2014
ERICO International Corporation.
3.3FT [1M]