ERICO ER Series 2m Stainless Steel Guyed Mast User Manual
Detail "a, Detail "b
®
Detail "A"
2
-
Preferred Angle
45° - 60°
Guy Kit (Optional)
(ERICO Part # GUYKIT4M/GRIP)
Do not over-tension guy wires
(Slightly sagging)
Stainless Steel Mast
(ERICO Part # ER22000SS)
Bonding Clamp
(ERICO Part # LPC570)
Mast Adapter
(ERICO Part # INTCPTSIIER2)
1
-
Stainless Steel Mast Base
(ERICO Part # ER2BASESS)
Refer to Detail "B"
SI INTERCEPTOR
(ERICO Part # SI25i, SI40i or SI60i
ER22000SS
ER2BASESS
Detail "B"
4 HOLES, Ø1/2 [12.5mm]
9 [229mm]
7 [178mm]
INTCPTSIIER2
1
-
®
Not to Scale
(ERICO Part # LPC805) Copper Strap
(ERICO Part # LPC126R) Copper Cable
(ERICO Part # A930W004) Drive-in Type Anchor
Typical LPC126R Cable Strap
Ground Inspection Well
Downconductor
(ERICO Part # LPC126R)
Lightning Event Counter
(ERICO Part # LECIV)
Bond to the existing
building ground system
ERICO CADWELD "GR" Connection
or mechanical connection
(ERICO Part # LPC790)
®
®
2/0 Conductor
(3 x 20FT [6.1M] length)
Enclosed in
ERICO GEM material
Minimum 5/8" X 8' [16mm X 2.4M] long
ground rod in three locations
Stainless Steel
Cable Tie
(ERICO Part # CABTIESS)
Three every 3.3FT [1M]
Lightning Event Counter
Refer to installation manual
for alternate locations
(ERICO Part # LECIV)
Two downconductors
are required
Not to Scale
LPC126R Copper Cable
LPC570 Bronze Pipe Bonding Clamp
Installing contractor to field
adjust and insure a secure bond
on highest ER series mast
Suggested triangular grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench
20FT [6.1M] in length and approximately 2.5FT [0.8M] deep. 20FT [6.1M] of 2/0 conductor is laid in the
trench and is connected to the ground rod using "GY" CADWELD connection. The conductor in
each trench is encased in ERICO GEM material. Ground rods must extend 10FT [3M] below ground
level.
Note: This is one of several alternative installation methods.
Refer to ERICO installation handbook for more details.
Mast Detail
For complete
grounding system
refer to Detail "A"
-
2
TECHNICAL SUPPORT
www.erico.com
IP79116_B
1 OF 1
INSTRUCTION SHEET
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com and from your ERICO customer service representative.
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be completely followed to ensure proper and safe installation and performance.
3.
Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and death.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
ERICO INTERCEPTOR SI25i, SI40i or SI60i
Installation Instructions for 2m Stainless Steel Guyed Mast - ER Series
© 2006, 2014
ERICO International Corporation.