beautypg.com

ERICO SIM Series Terminal Elevation: 4m Above Structure User Manual

Erico dynasphere mkiv, Detail "a

background image

1m

INTCPT ADAPTER

(ERICO Part # INTCPTMIDYN)

ERICO DYNASPHERE

(ERICO Part # D/SMKIV-SS)

®

Detail "A"

Stainless Steel Mast

(ERICO Part # SIM28A2)

Bonding Clamp

(ERICO Part # TMCSS)

SIM28A2

1

-

®

Ground Inspection Well

Downconductor

Lightning Event Counter

(ERICO Part # LECIV)

ERICO CADWELD Connection

or mechanical connection

®

®

3m tape enclosed in

GEM material

Minimum 16mm X 2.4m long

ground rod in four locations

Stainless Steel Cable Tie

(ERICO Part # CABTIESS)

Three every 1m

Lightning Event Counter

Refer to installation manual

for alternate locations

(ERICO Part # LECIV)

Two downconductors

are required

Not to Scale

Downconductor

TMCSS Mast Clamp

Installing contractor to

field adjust and insure a

secure bond on highest

SIM series mast

For complete

grounding system

refer to Detail "A"

Typical Conductor Connection

(ERICO Part # PDCUC) Tape Fasteners

(ERICO Part # TCEC253) Copper Tape

Not to Scale

3

-

Crow's Foot

(ERICO Part # GF302)

Stainless Steel Mast

(ERICO Part # SIM33B3)

Mast Support Bracket

(ERICO Part # ALOF1GS)

SIM33B3

-

2

Mast Detail

2 Holes, 10.9mm

39.9mm

89.9mm

119.9mm

Not to Scale

Typical ALOF1GS Wall Bracket Base

2

-

End View

3

-

1

-

Suggested triangular grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench

approximately 0.8m deep. The conductor is laid in the trench and is connected to ground rods. The

conductor in each trench is encased in GEM material. Ground rods must extend 3m below ground

level.
Note: This is one of several alternative installation methods.

Refer to ERICO installation manual for more details.

1m

TECHNICAL SUPPORT

www.erico.com

IP79153_A

1 OF 1

INSTRUCTION SHEET

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

ERICO DYNASPHERE MKIV

Installation Instructions for 5m Stainless Steel Cantilevered Mast - SIM Series

Terminal Elevation: 4m Above Structure

© 2014

ERICO International Corporation.

1m