ERICO TDSGABC14 Flange Mount Grounding Bus User Manual
Tdsgabc14, Flange mount grounding bus
Clean top and bottom surface of
flange using a T313 wire brush.
Remove all paint and oxide layers.
Install threaded rods by loosening hex bolt on
connector. Snug hex bolt by hand such that the rods
do not fall from the connector. Do not tighten hex bolt.
Loosen to install rods
3/8-16 Hex Nut
Belleville Washer
3/8" Flat Washer
Install inner hardware.
Apply12 ft-lbs (max)
Note: In the absence of a torque wrench, snug bolts
and tighten 1/4-turn.
Apply anti-oxide
compound at interface
Attach clamp. Tighten hex bolts then jam nuts as shown.
Flange Thickness Range: 1/4 to 1 inch
Flange Materials: Aluminum, Copper or Steel
TECHNICAL SUPPORT
www.erico.com
IP8250_B
1 OF 2
INSTRUCTION SHEET
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com and from your ERICO customer service representative.
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be completely followed to ensure proper and safe installation and performance.
3.
Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and death.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
TDSGABC14
Flange Mount Grounding Bus
© 2013 ERICO International Corporation.