Select proper lugs or splice connector for the size of cable being installed, make sure

1.

that the size matches the description in the table below.

Strip the insulation from the conductor to a length so that the stripped area of the

2.

conductor can be completely inserted into and fill the barrel of the lug or splice.

Carefully strip the insulation from the conductor without nicking the strands.

Wire brush the stripped portion of the conductor to remove oxide films.

3.

The stripped portion of the conductor must be clean and inserted completely into

4.

the connector barrel.

Using the tool and die combination specified for that in the table below, install

5.

crimps, leaving a space of 1/8" maximum between successive crimps unless

overlapped to fill the connector barrel at the referenced location illustrated.

Lug

Splice

Global Part No.

Cable Size

Die Color

Burndy® Y35

Die Sets

Burndy® Y35

Die Sets for

Smooth Weave

Die Index

---

8 AWG

Blue

U8CABT

---

374

ECLA6S14

6 AWG

Gray

U6CABT

---

346

ECLA4S14, ECLA4S516

4 AWG

Green

U4CABT

---

375

ECLA2S14, ECLA2S38

2 AWG

Pink

U2CABT

---

348

ECLA1S38, ECLA1S516

1 AWG

Gold

U1CART

---

471

ECLA1/0S38

1/0 AWG

Tan

U25ART

---

296

ECLA2/0S12

2/0 AWG

Olive

U26ART

---

297

ECLA3/0S12

3/0 AWG

Ruby

U27ART

---

467

ECLA4/0S12, ECLA4/0S14,

ECLA4/0S38, ECLA4/0S58,

ECLA4/0S516

4/0 AWG

White

U28ART

U28RT

298

ECLA250S516,

ECLA250S12, ECLA250S38,

ECLA250S58

250 MCM

Red

U29ART

U28ART

324

ECLA300S12

300 MCM

Blue

U30ART

---

470

ECLA350S12

350 MCM

Brown

U31ART

---

299

ECLA400S12

400 MCM

Green

U32ART

---

472

ECLA500S12

500 MCM

Pink

U34ART

---

300

ECLA600S58

600 MCM

Black

U36ART

---

473

ECLA750S58

750 MCM

Yellow Red

U39ART

---

936

TECHNICAL SUPPORT

www.erico.com

IP8242_B

1 OF 1

INSTRUCTION SHEET

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
Burndy is a registered trademark of Hubbell Incorporated.

ECLA

Installation Tooling for Dual Rated Aluminum Connectors

© 2012, 2013 ERICO International