ERICO MBNC240A Bonding Network Connector User Manual
Bonding network connector, Mbnc82, Mbnc240a
MBNC82
(MBNC82 Only)
(MBNC82 Only)
MBNC240
(Configurations for reference only)
MBNC240A attached to a metal plate
(Reference only)
MBNC82, MBNC240 and MBNC240A Installation:
Using a 5/8" deep well socket, torque nuts to 150 in-lbs [17 N-m].
1.
Conductors must extend at least 1" outside of connector.
2.
Install parallel conductors on the same plane (MBNC82 Only).
3.
CORRECT
INCORRECT
1. Stranded conductors #8 - #2 AWG: 7 or 19 strands
2. Solid Conductors: #2 AWG; Stranded Conductors #2 AWG 7 or 19 strands, #1 - 4/0 AWG: 7, 19 or 37 strands
MBNC240A
Part #
Conductor Type
Size
MBNC82
Solid, Stranded
1
8 - 2 AWG
MBNC240
Solid, Stranded
2
2 - 4/0 AWG
MBNC240A
Solid, Stranded
2
2 - 4/0 AWG
TECHNICAL SUPPORT
www.erico.com
IP8175_C
1 OF 1
INSTRUCTION SHEET
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com and from your ERICO customer service representative.
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be completely followed to ensure proper and safe installation and performance.
3.
Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and death.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
Bonding Network Connector
MBNC82, MBNC240 and MBNC240A
© 2010, 2012 ERICO International