ERICO EPD1224ATAAR (12/24Vdc, 30A) Secondary Surge Protector User Manual

Installation instructions, Secondary surge protector

background image

Secondary Surge Protector

2003 ERICO

Inc, 34600 Solon Rd, Solon, OH 44139

Page 1 of 1

Document Number: HBCR1661 Revision: 2

EPD1224ATAAR (12/24Vdc, 30A)


Installation Instructions

EPD

UNIT

BATTERY

CHARGER

SENSITIVE

ELECTRONICS

BATTERIES

5 3/4

4 3/4

5 1/4

3 1/2

2 3/8

2 3/8

2 3/8

3 1/2

AAR HARDWARE

SUPPLIED

MOUNTING SCREWS

SUPPLIED

FIG. 1

FIG. 2

FIG. 3

TWIST

WIRING

12/24 VDC PROTECTOR

www.erico.com

LINK OFF - 24V

LINK ON - 12V

= OK

ERICO PROTECTION DEVICES

R

TM

INPUT
NEG -

INPUT
POS +

OUTPUT

POS +

LINK

OUTPUT

NEG -

CAUTION !

30A MAX. IN-LINE, OR 60A TAPPED FROM INPUT TERMINALS

STATUS INDICATOR

1. Installation of Secondary Surge Protector (EPD unit)

should be by qualified personnel. Follow all applicable
electrical codes and procedures.

2. Disconnect and lockout power to the point where the

EPD unit is to be installed.

3. For 12V systems ensure the link from LINK terminal to

OUTPUT POS + terminal is installed. Line voltage
should not exceed 18 Vdc or the unit may be damaged.

For 24V systems ensure that the LINK terminal is not
connected to the OUTPUT POS + terminal. Line voltage
should not exceed 36 Vdc or the unit may be damaged.

12V

24V

LINK

NO LINK

Fig 4

4. Mount the EPD unit as close as possible to the sensitive

electronics being protected.

5. For mounting, use layout of holes as indicated in FIG. 1;

drill 9/64 diameter holes in the mounting surface for the
#8 x 1/2-lg. screws provided.

6. Output wires should be kept as SHORT as possible

between equipment and the EPD unit, and the input and
output wires should be twisted to minimize noise
coupling. Use A.A.R. hardware supplied. See FIG. 2 for
assembly.

7. Input and output wires to and from the filter unit should

be separated to minimize noise coupling.

8. EPD1224ATAAR does not have overcurrent protection.

The current in the circuit must not exceed the EPD unit
rating (30A).

9. The LED on the front panel illuminates to indicate that

the protection circuitry is operating correctly. If LED has
extinguished, the EPD unit has sustained a surge beyond
its ratings and the unit should be replaced immediately as
no protection may be provided.

10. Check wiring polarity matches EPD terminal marking.

Reverse polarity may damage the indication circuitry.
Engage power to the EPD unit. Status LED should
illuminate indicating correct operation. If not, disconnect
power, check wiring, EPD voltage selection link, rectify
any deficiencies, and reapply power. If still experiencing
difficulties, please contact your supplier, or the
manufacturer:

ERICO, Inc.
Rail Electrical Products
34600 Solon Rd
Solon OH 44139 USA
Ph. (800) 447-7245