beautypg.com

ERICO EPD100HZ120TDF (100Hz, 120 VAC) Fused Primary Surge Protectors User Manual

Installation instructions, Fused primary surge protectors, Parallel tvss filters

background image

Fused Primary Surge Protectors

Parallel TVSS Filters

1998 ERICO

Inc, 34600 Solon Rd, Solon, OH 44139

Page 1 of 3

Doc: HBCR1231DOC.DOC, Iss: 2, Date: 27JUL98

EPD25HZ120TDF (25Hz, 120 VAC)

EPD100HZ120TDF (100Hz, 120 VAC)


Installation Instructions

FORM C

CONTACTS

CABLE ENTRY

COM
NC
NO

MOUNTING SCREWS

SUPPLIED

6

6

FIG. 1

FIG. 2

FIG. 3

10 3/4

11 1/2

8 1/2

9 1/4

3 3/4

UNIT OPERATING S TATUS

120 VAC - 100 HZ

PANEL PROTECTOR

STAGE 1

STAGE 1

STAGE 2

STAGE 2

FORM 'C'

CONTACTS

NC

COM

NO

LINE 1

LINE 2

E R I C O

P R O T E C T I O N

D E V I C E S

R

TM

INPUT

OUTPUT

EPD

L1

L1

L1

L2

L2

L2

G

G

G

1

2

3

4

PREPARATION

DANGER: Electrical shock or burn hazard.
Installation of Primary Surge Protector should be
made by qualified personnel. Failure to lockout

electrical power during installation or maintenance can
result in fatal electrocution or severe burns.

1. Disconnect and lockout power to the breaker box (load

center) or point where the Primary Surge Protector is to
be installed. Follow all applicable electrical codes &
procedures.

CAUTION: Check to make sure line voltage does
not exceed Surge Protector voltage requirement.
Note also the AC frequency requirements of these

Surge Protectors.

PROTECTOR MOUNTING AND LOCATION

2. The Surge Protector is to be mounted as close to the

power entrance point as possible to maximize
performance.

3. The Surge Protector can be attached directly to a wall

panel:

a) Drill 3/16 diameter pilot hole in the wall panel. See

FIG. 1 for mounting hole configuration.

b) Mount unit with (4) #12 x 3/4-lg. screws supplied.

See FIG. 2

AC ELECTRICAL CONNECTION

4. The Surge Protector should be wired as shown in FIG. 3

to provide maximum performance. This allows for a
“zero” lead length or Kelvin connection to the Surge
Protector. When using this recommended method, use
the two outer knockouts, so that the input wiring enters
on one side, and the output wiring exits on the other side.
It is possible to wire the unit parallel to the supply. In
this case, tap conductors are run into the unit (the single
center knockout may be used), and only one wire lead
terminates on each wiring terminal. This method does
not provide the optimum surge performance of the
recommended Kelvin connection method.

NOTE: Where a supply transformer is used, the Surge
Protector should be placed on the load side of the supply
transformer for optimal performance.

5. The knockouts are sized to fit 1” fittings, but may be

enlarged if necessary to take larger fittings. The
terminals will accept wiring up to #2 AWG, but the
maximum wire size possible will be determined by the
type of wire and the fitting size used. Ensure that the
wiring size chosen meets applicable codes.

NOTE: The Surge Protector must be properly and securely
connected to the system ground. Note also that there is no
neutral connection available on this unit.

This manual is related to the following products: