ERICO TDX50 Series User Manual
Installation instructions

Installation Instructions
TDX50 Series
34600 Solon Road
HBCR1591 REV 5
Solon, Ohio 44139
(440) 248-0100
www.erico.com
This CRITEC TDX50 Surge Protection Device (SPD) is a high-performance Transient Voltage Surge 
Suppressor (TVSS), designed to provide protection for sensitive electronic loads connected to distribution 
panelboards or switchboards or where the SPD is directly connected to the electronic device. Maximum 
protection will only be achieved if the SPD is properly installed. Please read the installation instructions 
carefully and follow the instructions. 
 
DANGER: Electrical shock or burn hazard. The installation of this TVSS device should 
be made by qualified personnel. Failure to lockout electrical power during installation or 
maintenance can result in fatal electrocution or severe burns. 
 
CAUTION: Check to make sure line voltage does not exceed TVSS voltage 
requirement. 
 
CAUTION: This unit must be installed in accordance with the National Electrical Code 
(ANSI/NFPA-70) and applicable local codes, and must be installed on the load side of 
the main over-current protection. 
 
CAUTION: Do not install on ungrounded electrical systems. 
 
 
NOTICE: Do not cut wires until the SPD is mounted and minimum wire lengths have been verified. All
connection leads should be cut to minimum possible length; never coil or push aside excess 
length. 
INSTALLATION INSTRUCTIONS 
 
1. Verify line voltage by measuring L -N, L-G, 
L-L and N -G of the system. Confirm that the 
SPD is correctly rated for the system to 
which it is to be connected by comparing the 
measured voltages to the SPD voltage 
ratings shown on the product side rating 
label. The (MCOV) maximum continuous 
operating voltage specifications must not be 
exceeded. 
 
2. Identify proper location for SPD. Locate as 
close as physically possible to panel being 
protected. Mount top and bottom SPD 
flanges securely. Mount as close to the 
electrical connection as possible avoiding 
excess distance and avoiding the need for 
sharp bends in the wires. (Note: Refer to 
installation diagram on SPD.) Use 
appropriate conduit fittings to preserve the 
SPD/panel NEMA enclosure rating. 
3. Connect proper ground. An insulated
grounding conductor that is identical in size 
and insulating material and thickness to the 
grounded and ungrounded circuit supply 
conductors, except that it is green with or 
without one or more yellow stripes, is to be 
installed as part of the circuit that supplies 
the filter. The TDX is supplied with 914mm 
(3ft) long of #10AWG, in accordance with 
Table 250-122 of the National Electrical 
Code", for this purpose. The housing of the 
TDX unit is bonded to the grounding 
conductor for equipment safety ground 
purposes as per National Electrical Code. 
The grounding conductor is to be grounded 
to earth at the service equipment or other 
acceptable building earth ground such as the 
building frame in the case of a high-rise 
steel-frame structure. 
Attach the grounding conductor to the 
panel’s ground bus for proper operation. 
Wire length should be minimized to improve 
performance. There is no minimum wire 
length requirement. 
 
Note: For isolated ground systems, bond the 
grounding conductor from the TDX unit to 
the non-isolated equipment ground, not the 
isolated equipment ground.
