ERICO SES40P Series SPD User Manual

Ses40p series

background image

INSTRUCTION SHEET

DANGER
ELECTRICAL SHOCK OR BURN HAZARD. HAZARDOUS VOLTAGES EXIST INTERNAL TO THE SES40P. THIS UNIT SHOULD BE INSTALLED AND SERVICED ONLY BY QUALIFIED PERSONNEL IN
CONFORMANCE WITH ALL GOVERNING CODES AND INSTRUCTIONS. FAILURE TO LOCKOUT ELECTRICAL POWER DURING INSTALLATION OR MAINTENANCE CAN RESULT IN FATAL
ELECTROCUTION, SEVERE BURNS, OR OTHER INJURIES. BEFORE WORKING WITH OR MAKING ANY CONNECTIONS TO THIS DEVICE, BE SURE THAT POWER HAS BEEN REMOVED FROM ALL
ASSOCIATED WIRING, ELECTRICAL PANELS, AND OTHER ELECTRICAL EQUIPMENT.

1. The power supply to the SES40P should always be turned (and locked) OFF before the unit is accessed for any reason.
2. Prior to installation, ensure that the SES40P is of the correct voltage, current, phasing, and frequency for the applicable rating of the power distribution system.
3. This unit may be installed on the load side or the line side of the main over-current protection provided that it is not installed on services with more than 200kA fault current capability.
4. Diagrams are for reference only. Schematics are representative of typical applications and are only to be used for reference.

WARNING
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

www.erico.com

and from your ERICO customer service

representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause product malfunction, property damage, serious bodily injury and death.

SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to
the application.
ANSI is a registered trademark of American National Standards Institute
NEC is a registered trademark of, and National Electrical Code (NEC) standard is a copyright of the National Fire Protection Association
NFPA is a registered trademark of National Fire Protection Association
UL is a registered trademark of Underwriters Laboratories, Inc.

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are registered trademarks of ERICO International Corporation

TECHNICAL SUPPORT:

www.erico.com

IP8213_B 1 of 2

2011 ERICO International Corporation

SES40P Series


The SES40P Series of Surge Protective Devices (SPD) are UL
1449 Ed. 3 Type 1 devices designed to provide protection to
service panels, load centers or where the SPD is directly
connected to the electrical device requiring protection. The
SES40P Series SPD is UL Type 4X rated, and is supplied with
24” wiring leads for a direct hardwired connection. Maximum
protection will only be achieved if the SPD is properly installed.
Please carefully read and follow the installation instructions.

DANGER: Electrical shock or burn hazard.

Installation of this SPD should only be made by qualified
personnel. Failure to lockout electrical power during
installation or maintenance can result in fatal electrocution or
severe burns.

CAUTION: Check to make sure system voltages

do not exceed the SPD voltage requirement and ratings and
that the correct SPD voltage/model has been selected.

CAUTION: This unit must be installed in

accordance with the National Electrical Code (NEC)
(ANSI/NFPA-70) and all other applicable codes.

SES40P Series SPD

CAUTION: Ungrounded power systems are

inherently unstable and can produce excessively high line-to-
ground voltages during certain fault conditions. During these
fault conditions any electrical equipment, including an SPD,
may be subjected to voltages that exceed their designed
ratings. This information is being provided to the user so that
an informed decision can be made before installing any
electrical equipment on an ungrounded power system.

NOTE: Do not cut wires until the SPD is mounted and
minimum wire lengths have been verified. All connection leads
should be cut to minimum possible length; never coil or push
aside excess length.


Installation Instructions

1. Verify system voltage Confirm that the SPD is correctly

rated for the system to which it is to be connected by
comparing measured voltages to the SPD voltage ratings
shown on the product rating label. The measured voltage
should match the nominal operating voltage of the product,
the maximum continuous operating voltage (MCOV)
specifications must not be exceeded.


2. Identify proper location for the SPD. Locate the unit as

close as possible to the panel being protected to minimize
lead lengths. If possible, avoid sharp bends in wires. The
SES40P is supplied with an integral ¾” threaded nipple and
conduit locknut. The SES40P can be direct nippled into the
panel, and secured with the locknut. If required, use
appropriate watertight conduit hubs to maintain the
SPD/panel UL enclosure rating.


3. Connect ground. Attach the grounding conductor to the

panel’s ground bus. Wire length should be minimized to
improve performance. There is no minimum wire length
requirement.

Note 1: The SES40120/240SP does not have a grounding
conductor, it utilizes a grounded (neutral) conductor for
operation.

Note 2: For isolated ground systems, bond the grounding
conductor from the SES40P unit to the non-isolated
equipment ground, not the isolated equipment ground.


4. AC Rated Units: Connect neutral and phase

conductors. The SES40P SPDs are supplied with 24” of
12AWG leads for a direct hardwired connection. With the
POWER OFF, connect the neutral conductor of the SPD to
the neutral lug in the panel. Connect each black lead
(phasing is not critical to the operation). Wire lengths
should be minimized to improve performance. There is no
minimum wire length requirement. The SES40P Series of
SPDs are rated as a UL 1449 Ed 3 Type 1 device and
therefore no overcurrent protection is required. However, if
overcurrent protection is desired, then a 20A fuse or circuit
breaker is recommended.