beautypg.com

Installation after the main disconnect, Installation before the main disconnect – ERICO CRITEC SES65 240 AC Panel Protector User Manual

Page 3

background image

3

Phone: 800-248-9353
www.erico.com

INDOOR/OUTDOOR INSTALLATION & OPERATING INSTRUCTIONS

SES65 120/240 AC Panel Protector

HOT

NEUTRAL

HOT

GROUND

BLACK

GREEN

BUILDING
GROUND

120V

240V

120V

USE BUS TO CONNECT GROUND
WIRES FOR TELCO OR COAX LINES

METER

30 A BREAKER OR
SUB-FEED LUG SET

B

B

B

MAIN
DISCONNECT

FROM SES65 120/240

GROUND BUS

30 A BREAKER
OR SUB-FEED

Figure 2

Figure 3

Installation BEFORE The Main Disconnect

WARNING: REMOVE THE METER OR OTHERWISE DISCONNECT THE AC POWER BEFORE
BEGINNING THE INSTALLATION!!!

The SES65 120/240 should be installed by qualified and authorized personnel.

USE A TEST LAMP TO CONFIRM THAT THE POWER HAS BEEN REMOVED!!

The SES65 120/240 protector is UL Listed for installation either before or behind the main
service disconnect. The mechanical installation to the meter pan or meter side of the serv-
ice panel is as described in figures 1- 3, as close as possible to the wiring between the
meter and the service disconnect.

SES65 120/240 CONNECTIONS:

1. The SES65 120/240 wires should be connected to the points "B" in figure 4. The

connections can be made at the meter socket or on the wiring to the main disconnect.

2. Connect the green (ground) wire to the service raceway, the ground bus, or any other

part of the grounding electrode system. The ground wire should be kept as short as
possible.

3. Connect the 2 black wires to the two phase terminals of the meter socket or to the

conductors to the disconnect. An insulated tap connector such as ILSCO KUPLER IPC 4/0-#6
is a fast and easy way to connect the black (phase) wires to the service conductors.

4. Check the connections!
5. Replace the meter, or turn the AC power switch back on.The two green lights on the

unit should come on, confirming that the connections are correct and there is power
to both phases.

Installation AFTER The Main Disconnect

1. The SES65 120/240 should be installed by a qualified electrician.

2. Turn "OFF" and lock out the power to the enclosure in which the unit is to be installed.

3. Connect the green wire to the ground bus or connector.
4. Install the appropriate 2 pole, 30 ampere circuit breaker or lug kit (See table) to the

panelboard or meter combination device. If a sub-feed lug kit is available, it is a better
and more economical connection than a breaker.

5. Connect the black leads to the load terminals of the circuit breaker or lug kit and tighten

to the required torque.

6. Double check connections, then reconnect power.

7. When both LEDs are on, the protector is functioning as desired.

WIRING SCHEMATIC

RECOMMENDED BRANCH CIRCUIT BREAKER

SIEMENS / GOULD / ITE

ITE PUSHMATIC

MURRAY / CROUSE-HINDS
SEARS

GE

SQUARE D QO

SQUARE D HOMELINE

CUTLER-HAMMER CH

CUTLER HAMMER BR
CHALLENGER
SYLVANIA / WESTINGHOUSE

THOMAS & BETTS / BRYANT

SIEMENS

SIEMENS

MURRAY

GE

SQUARE D

SQUARE D

CUTLER-HAMMER

CUTLER HAMMER

THOMAS & BETTS

Q230

P230

MP230

THQL2130

QO230

HOM230

CH230

BR230

TB230

If your panel is: Manufacturer Catalog Number

This manual is related to the following products: