ERICO IP8007 Horizontal Tap Perpendicular to Flange User Manual
ERICO Accessories for electrical
Rail
Prior to making a connection, read and follow the full instruction sheet IPRF, the full
instruction sheet shipped with ERICO CADWELD (IPX) and special instructions
below.
For better fit of mold to rail, rub mold along rail.
1.
Place cable in mold and lock "E-Z" clamp.
2.
Check that mold fits snug against rail. Cable should touch the rail.
3.
Hold mold to rail.
4.
Pack all openings between mold and rail which may leak molten metal with
5.
mold sealant material from ERICO (ERICO part number T403).
Follow standard welding procedures.
6.
Mold
Conductor
®
®
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT:
www.erico.com
IP8007_B
INSTRUCTION SHEET
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
1 OF 1
© 2006, 2014
ERICO International Corporation
WARNING:
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
www.erico.com and from your ERICO customer service representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
damage, serious bodily injury and death.