ERICO IP7748 Cable to Lug Horizontal Tap Perpendicular to Flange User Manual
ERICO Accessories for electrical
4" [101.6 mm] min.
.5 X 2" Lug
[12.7 x 50.8 mm]
Mold Bottom
Figure 2
Place Lug in
Mold Bottom
Figure 3
Figure 4
Top Section of Mold
Toggle
Figure 5
Cover
Ignite Starting
Material Here
Figure 6
Prior to making a connection, read and follow the full instruction sheet IPR
F,
the full instruction sheet shipped with CADWELD (IPX), and special instructions below.
Degrease and grind area of rail to be welded (Figure 1).
1.
Clamp mold bottom to rail, adjust vise grip to be snug. Check to ensure proper tension (Figure 2).
2.
Place .5" X 2" [12.7 mm x 50.8mm] lug in mold bottom. Lug hole will fit onto bolt in mold for
3.
positioning (Figure 3).
Lock top mold section together, insert disk and welding material. Place starting material on
4.
welding material and crucible lip (Figure 4).Close cover (As shown in Figure 6) and ignite starting
material.
®
Figure 1
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT:
www.erico.com
IP7748_C
INSTRUCTION SHEET
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
1 OF 1
© 2002, 2012, 2013
ERICO International Corporation
WARNING:
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
www.erico.com and from your ERICO customer service representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
damage, serious bodily injury and death.
Cable to Lug Horizontal
Tap Perpendicular to
Flange