ERICO IP7069 Type PL and DS Specia User Manual
Type pl and ds special, Detail a without sleeve, Detail b with sleeve
Detail A
Without Sleeve
Gap as Noted
Lug
of Tap Hole
Center
Conductor
Detail B
With Sleeve
Gap as Noted
Lug
of
Tap
Hole
Center
Conductor
T403 Mold Sealer .13" [3.2mm]
®
Prior to making a connection, read and follow the full instruction sheet IPRNS, the full
instruction sheet IPP, the full instruction sheet shipped with CADWELD (IPX), and
special instructions below.
Position mold on cables and lug with lug positioned as shown above (lug notch
1.
facing down). Gap lug and cable directly under tap holes. Gap is noted on mold
tag. (See Detail A).
When sleeve is used, insert sleeve on cable. Let cable end protrude .13" [3.2
2.
mm] beyond end of sleeve (See Detail B). Position sleeve and cable into mold
with flare of sleeve against counterbore wall. Use ERICO mold sealer (ERICO
part number T403) to fill openings in cable.
When using special frames, lock top halves of mold together. Then lock top and
3.
bottom sections together.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT:
www.erico.com
IP7069_E
INSTRUCTION SHEET
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
1 OF 1
©1995, 2000, 2005, 2013
ERICO International Corporation
WARNING:
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
www.erico.com and from your ERICO customer service representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
damage, serious bodily injury and death.