background image

1

40 in-lbs [4.5 Nm]

2

3

P 150 in-lbs [17N-m]

P 150 in-lbs [17N-m]

Installation:

For simplest installation CADDY® CAT LINKS J-Hooks, if specified, should be attached to pedestal

1.

clamp before installation on the pedestal.

Attachment of clamp to pedestal:

2.

Secure nuts finger tight approximately equal distance on L-bolt.

Using a 9/16" wrench or socket, torque nuts to 40 in-lbs [4.5 N-m]

Conductor installation in MBNUPCJ82

3.

Install parallel conductors on the same plane.

Using a 5/8" deep well socket torque nuts to 150 in-lbs [17 N-m]

Conductors must extend at least 1" outside of connector

CORRECT

INCORRECT

X

(MBNUPCJ82 Only)

(MBNUPCJ82 Only)