INSTALLATION INSTRUCTIONS
Installation Overview:

Recommended electrical requirements for

monitor:

Power and Ground wire gauge and length: Distance Ft.(m) Wire Gauge (AWG)

100(30.5) – 150(45.7)

8

50(15.2) < 100(30.5)

10

25(7.62) < 50(15.2)

14

< 25(7.62)

16

Power and Ground wire type: Cross Link or equivalent (Must meet or exceed NFPA 1901 Section 13)

Maximum monitor amperage draw: 20 AMPS

CAN wire gauge and length:
o

Main Line: 131 ft. (40 m) – 18-20 AWG (Must meet J1939 specification)

o

Branch (node) Line: 3 ft. (1 m) – 18-20 AWG (Must meet J1939 specification)

CAN wire type and shielding: Twisted shielded pair - 105°C 150V (Belden 9841 series or equivalent)
o

Shield Drain: Connect shield/drain to pin C of J1939 connector

Recommended electrical requirements for the 7000 series input devices:

Power and Ground wire gauge and length: 18-20 AWG 105°C 150V up to 150 ft. (45.7 m)

Maximum input controller amperage draw: 500mA

CAN wire gauge and length: 3 ft. (1 m) – 18-20 AWG

CAN wire type and shielding: Twisted shielded pair - 105°C 150V (Belden 9841 series or equivalent)
o

Shield Drain: Connect shield/drain to pin C of J1939 connector

Docking station wire gauge type: 20 AWG cross link or equivalent

Termination Points:
When using CAN lines for communication there must be 2 termination points within the system.

Termination points are explained further in the Configuration section (installation step 2). What is

important at this time is that in order to maximize the efficiency of communication in your CAN

network, you must terminate the two components at the extreme ends of your main CAN line. This

should be taken into consideration as you setup your EXM system. Each additional EXM component that

requires connection to the main CAN communication line between the two end components will

require the use of CAN Connector Kit (P/N 37221000). The maximum length of wire from the main

CAN line is 3ft. and would be considered a branch (node) off the main CAN line.

CAN Connector Kit:

You may install any of the EXM CAN components that require

the use of a CAN Connector Kit (P/N 37221000) by plugging

the tri-pin CAN connector from the EXM component directly into

the wye connector (Deutsch DT04-3P-P007) of the CAN

Connector Kit. You can also use the crimp connectors on the

mating connector leads to make your own connection.

Step 1 – Mount and Wire All System Components
Step 2 – Configure the EXM System (If Required)
Step 3 – Calibrate the EXM System
Step 4 – Check Installation