Elkhart Brass Cobra 7200 EXM Monitor User Manual
Page 32

32
SYSTEM SPECIFICATIONS
7200 EXM Monitor
Max Flow Rating
1250 GPM (4731 LPM)
Max Operating Pressure
250 PSI Continuous (17.2 BAR)
500 PSI Limited Duty (34.5 BAR)
[50% / 1hr (30min on / 30 min off)]
Inlet Size
3”-150# Flange, DN80-PN16 Flange, 4”-150# Flange,
3” NPT, 3” BSPT
Outlet Size
2.5” Male NHT, 2.5” Male BSPP
Travel
V: -45° to +120°
H: L175° to R175°
Movement
Sealed Electric Motors
Swing Radius
6”
Stow Height
16”
Weight
31 Lbs.
Operating temperature range
-40°F to +185°F (-40°C to +85°C)
Environmental Rating
NEMA 4
Monitor Controller
Input power
12/24 VDC (11-27 VDC)
Control Communication
CAN bus J1939
2.4 Ghz digital radio frequency (unlicensed)
Electrical Load
See Table 1 Below
Fuse Rating
20 AMPS (12V) & 10 AMPS (24V)
RF power output
Meets FCC part 15 requirements for license free operation
Operating temperature range
-40
o
F to +185
o
F (-40
o
C to +85
o
C)
Environmental Rating
NEMA 4
FCC ID
KQL-2510100
7200 SD – Standard Duty Motors
Motor (12 VDC)
Left/Right
Up/Down
Nozzle
Run Current
3 A
3 A
0.5 A
Stall Current
10 A
10 A
NA
Current Trip Point
6.5 A
6.5 A
4 A
7200 HD – Heavy Duty Motors
Motor (12 VDC)
Left/Right
Up/Down
Nozzle
Run Current
5 A
5 A
0.5 A
Stall Current
70 A
70 A
NA
Current Trip Point
20 A
20 A
4 A
Table 1: Motor Current Specifications
Panel Mount Controller - 7010
Input power
12/24 VDC (11 VDC to 27 VDC)
Electrical Load
0.5 AMPS
Fuse Rating
1 AMPS (12V) & 0.5 AMPS (24V)