Elkhart Brass Cobra 7200 EXM Monitor User Manual
Page 29
![background image](/manuals/558219/29/background.png)
29
Press and release the PRESET button
The input controller will read the hex file on the flash drive and install it as long as the copied
firmware is newer than the existing firmware.
o
This process will likely take up to ten minutes to complete. If using an RF input controller,
update time may be up to three times as long.
o
This action will also update all input controllers on the CAN line (primary and secondary)
o
Once all of the input controllers are updated and there were no errors while upgrading; then
the preset LED will blink once every three (3) seconds.
o
If the primary input controller does not recognize it as newer firmware, then no update will
take place and the preset LED will flash twice every three (3) seconds.
o
If the update did not perform correctly, the preset LED will blink three times every three (3)
seconds. If the update did not perform correctly please call Elkhart Brass at (800) 346-
0250.
Remove the USB flash drive from the input controller to exit USB Mode. (On older systems it may
be necessary to push the right button on the panel mount or hand held, or move the joystick
right, to exit USB mode).