beautypg.com

Despatch MIC1422 Controller User Manual

Page 81

background image

77

DC
Resolution:

Eight bits in 250 mS (10 bits in 1 second typical, >10 bits in
>1 second typical).

Update Rate:

Four times per second

Ranges:

0-20 mA, 4-20 mA, 0-10 V, and 0-5 V
NOTE: Changes between V and mA ranges also require jumper movement.

Load Impedance:

0 - 20 mA: 500 ohm maximum

4 - 20 mA: 500 ohm maximum
0 - 10 V:

500 ohm minimum

0 - 5V:

500 ohm minimum

Isolation:

Isolated from all other inputs and outputs.

Transmitter Power Supply Rating: 24 VDC, 20 mA maximum

Control Specifications


Control Types:

RaPID, PID, PID/On-OFF2, ON-OFF

Automatic Tuning
Types:

Pre-Tune and Auto-Tune

Proportional Bands:

0 (OFF), 0.5% - 999.9% of input span @ 0.1% increments

Auto Reset:

1 s - 99 min 59 s/repeat and OFF

Rate:

O (OFF) - 99 min 59 s

Manual Reset:

Adjustable in the range 0-100% of output power (single
output) or -100% to +100% of output power(dual output)

Deadband/Overlap:

-20% to +20% of proportional band 1 + proportional band 2

ON/OFF Hysteresis:

0.1% to 10.0% of input span

Auto/Manual Control:

User-selectable with "bumpless" transfer into and out
of Manual control.

Cycle Times:

Selectable for 0.5s to 512s in binary steps

Setpoint Range:

Limited by Setpoint Upper and Setpoint Lower limits

Setpoint Maximum:

Limited by Setpoint and Range Upper Limits

Setpoint Minimum:

Limited by Range and Setpoint Lower Limits

Setpoint Ramp:

Ramp rate selectable 1-9999 LSDs per hour and infinite.
Number displayed is decimal point aligned with selected
range.