beautypg.com

Despatch MIC1422 Controller User Manual

Page 6

background image

2

1.2 Displays


Each instrument is provided with dual displays and status indicators as shown in Figure
1 -1. The upper display (RED) displays the value of the process variable. The lower
display (GREEN) displays the setpoint value.

1.3 Control


The instrument can be programmed for on-off, time proportioning, or current
proportioning control implementations depending on the model number. A second
control output is an available option. Proportional control implementations are provided
with fully programmable PID parameters.

1.4 Alarms


Alarm indication is standard on all instruments. Up to two alarm outputs are possible.
Alarm type may be set as Process Direct or Reverse (high or low), Deviation Direct or
Reverse (above or below setpoint), Deviation Band Type (closed or open within band),
or Loop Reverse or Direct. Alarm status is indicated by LED. An Alarm Inhibit is
provided to prevent, when activated, unwanted alarms during power-up.