beautypg.com

Despatch MIC1422 Controller User Manual

Page 77

background image

73

APPENDIX D: SPECIFICATIONS

Input Specifications


General
Input Sample Rate:

Four per second

Input Resolution:

14 bits approximately

Input Impedance:

Greater than 100M ohm resistive (except for
DC mA and V inputs)

Isolation:

Universal input isolated from all outputs except
SSR at 240 VAC


Thermocouple Inputs
Thermocouple Types:

R, S, J, T, K, L, B and N
Note: Thermocouple must not be grounded! Damage to
the cold junction in the control will result!

Calibration:

Complies with BS 4937, NBS125 and IEC584.

Sensor Break Protection:

Break detected within 2 seconds. Control outputs set to OFF
(0% power); alarms operate as if the process variable has
gone over-range.


RTD and DC mV Inputs
Type and Connection:

Three-wire Pt100

Calibration:

Complies with BS1904 and DIN43760.

Lead Compensation:

Automatic

RTD Sensor Current:

200 mA (approximately)

Sensor Break Protection:

Break detected within 2 seconds. Control outputs set to OFF
(0% power); alarms operate as if the process variable has
gone under-range.


DC mA and DC V Inputs
Scale Range Maximum:

-1999 to 9999

Scale Range Minimum:

-1999 to 9999

Minimum Span:

1 display LSD

Sensor Break Protection:

Applicable to 4-20 mA, 1-5V, and 2-10V ranges only. Break
detected within 2 seconds. Control outputs set to OFF (0%
power); alarms operate as if the process variable has gone
under-range.