Page 7: 3 parity, 4 stop bits, 5 baud rate, Serial communications settings -4

1.2.2
Serial Communications Settings
1.2.2.1 Configuration
•
RS-232
•
RS-485 (Default)
1.2.2.2 Data
Bits
•
7 bits
•
8 bits (Default)
The Data Bits setting should match the Transmission Mode as
follows. The ability to set the Data Bits independent of
Transmission Mode is to allow for maximum flexibility.
•
RTU
8 Data Bits
•
ASCII
7 Data Bits
1.2.2.3 Parity
•
EVEN (Default)
•
ODD
•
NONE
1.2.2.4 Stop
Bits
•
1 (Default)
•
2
1.2.2.5 Baud
Rate
•
2400
•
9600 (Default)
•
19200
•
38400
•
57600
•
115200
Note: The Modbus specification requires the use of 2 Stop Bits when
No Parity is selected.
20959-01 Rev 02
Page 1-4