beautypg.com

I. pre-installation – Burnham 81433101R16-1/10 User Manual

Page 6

background image

6

A

. INSPECT SHIPMENT carefully for any signs of

damage.
1. ALL EQUIPMENT is carefully manufactured,

inspected and packed. Our responsibility ceases

upon delivery of crated boiler to the carrier in good

condition.

2. ANY CLAIMS for damage or shortage in shipment

must be filed immediately against the carrier by the

consignee. No claims for variances from, or shortage

in orders, will be allowed by the manufacturer

unless presented within sixty (60) days after receipt

of goods.

B

. LOCATE BOILER in front of final position before

removing crate. See Figure 1. Boiler's approximate

shipping weight is 325 pounds.
1. LOCATE so that vent pipe will be short and direct.

Refer to Section V. A., General Venting Guidelines.

2. BOILER IS SUITABLE FOR INSTALLATION

ON COMBUSTIBLE FLOOR. Boiler cannot be

installed on carpeting.

3. FOR BASEMENT INSTALLATION, provide a

solid base, such as concrete, if floor is not level, or if

water may be encountered on floor around boiler.

4. PROVIDE SERVICE CLEARANCE of at least 24”

at front of boiler for servicing.

5. For minimum clearances to combustible materials,

see Figure 2.

C

. PROVIDE COMBUSTION AIR SUPPLY to

accommodate proper combustion of oil. Local and

national codes may apply and should be referenced.

I. Pre-Installation

1. In unconfined spaces (basement) in buildings of

conventional frame, brick, or stone construction,

infiltration normally is adequate to provide air for

combustion. An unconfined space is a space whose

volume is greater than or equal to 50 cubic feet

per 1000 BTUH of the combined input of all air

consuming appliances in the space.

2. In a confined space, combustion air may be ducted

directly from the outdoors to the burner. Refer to

Section IV for installation of air intake duct to the

burner.

D

. VENTILATION AIR must be provided to maintain the

ambient temperature at safe limits. Local and national

codes may apply and should be referenced.
1. In unconfined spaces (basement) in buildings of

conventional frame, brick, or stone construction,

infiltration normally is adequate to provide air for

ventilation.

2. In confined spaces (closet, etc.) two permanent

openings, one near the top of the enclosure and one

near the bottom, shall be provided. Each opening

shall have a free area of not less than 1 sq. inch per

1000 BTUH of the total input of all appliances in the

space.

E

. Do not install boiler where gasoline or other flammable

vapors or liquids, or sources of hydrocarbons (i.e.

bleaches, cleaners, chemicals, sprays, paint removers,

fabric softeners, etc.) are used or stored.