CAUTION

Operation of boiler with improperly adjusted

burner may result in soot damage to side of

house.

6. Intake Terminal Location (Direct Vent only) -

Locate Air Intake Terminal not less than 12 inches

to the left, right, or bottom of the vent terminal. Do

not locate air intake terminal above vent terminal.

Intake terminal must be at least 12 inches above

grade plus snow accumulation; at least 1 foot from a

roof soffit; at least 3 feet from an inside corner of an

L-shaped structure. See Figure 9.

7. The LEDV must be vented with 4" Z-Flex Direct

Oil™ Vent. 20 feet is the maximum vent length

allowed. The vent pipe is available in 5, 10, 15, and

20 foot lengths. Table 1 lists vent part numbers.

Figure : Intake Terminal Location

Components of this kit are listed in the Repair Parts

Section of this manual.

DANGER

Vent pipe may not be spliced. Do not drill through

vent pipe. Do not operate boiler if vent pipe has

been crushed. Vent pipe must be completely

sealed. Do not operate boiler if vent pipe insulation

sleeve is damaged, frayed or missing.

B.

Vent Installation (Direct Vent and Side-Wall Vent)

1. Install Vent Terminal. See Figure 10.

a. After determining the location from previous

Section, cut an opening in the wall for the vent

terminal.

Combustible wall: 8 inches diameter hole

is required to maintain a 1 inch clearance to

combustible materials.

Non-combustible wall: 6½ inches diameter

hole is required.

b. Secure 10" square trim plate to outside wall.
c. Insert the vent terminal through the opening until

the stop bead rest against the trim plate.

d. Slide the 10" square inside trim plate assembly

(fitted with gear clamp) onto the terminal pipe.

Table 1: Vent Pipe Part Numbers

4" Direct Oil™ Vent Pipe

Pipe Length

Part No.

5 Ft.

8113302

10 Ft.

8113303

15 Ft.

8113304

20 Ft.

8113305

8. The vent system must be completed with the Direct

Oil™ Vent Kit, which is shipped with the boiler.