beautypg.com

Notice, Warning, Important – Burnham 81433101R16-1/10 User Manual

Page 27

background image

of a faulty cut-off valve in the fuel pump, or it

may be air trapped in the nozzle line. It may take

several firing cycles for that air to be fully vented

through the nozzle. Water in the fuel or poor

flame shape can also cause shut down noises.

NOTICE

CHECK TEST PROCEDURE. A very good test for

isolating fuel side problems is to disconnect the

fuel system and with a 2 foot length of tubing, fire

out of an auxiliary five gallon pail of clean, fresh,

warm # oil from another source. If the burner runs

successfully when drawing out of the auxiliary

pail then the problem is isolated to the fuel or fuel

lines being used on the jobsite.

G

. TEST CONTROLS

WARNING

Before installation of the boiler is considered

complete, the operation of all boiler controls must

be checked, particularly the primary control and

high limit control.

1. CHECK THERMOSTAT OPERATION. Raise and

lower thermostat setting as required to start and stop

burner.

2. VERIFY PRIMARY CONTROL SAFETY

FEATURES using procedures outlined in

Instructions furnished with control (See back of

Control Cover) or Instructions as follows:

WARNING

FOR HEATING SERVICEMAN

ONLY

a. Simulate flame failure:

Follow the starting procedure to turn on the

burner.

Close the hand valve in the oil supply line.

Safety switch should lock out in

approximately 15 seconds. Ignition should

stop and oil valve should close. Blower will

stop after postpurge period.

Push red reset button to reset safety switch.

b. Simulate ignition failure:

Follow the starting procedure to turn on the

burner, but do not open the oil supply hand

valve.

Safety switch should lock out in

approximately 15 seconds. Ignition and

motor should stop and oil valve should

close.

Push red reset button to reset safety switch.

c. Simulate power failure:

Follow the starting procedure to turn on the

burner.

With the burner running, turn off the power

to the system by tripping the circuit breaker

or removing the fuse.

Burner should stop.

Restore power. Burner should start.

d. If system does not operate as described, go to the

TROUBLESHOOTING AND MAINTENANCE

section.

3. VERIFY HIGH LIMIT OPERATION.

a. Adjust thermostat to highest setting.
b. Observe temperature gauge. When temperature

is indicated, adjust limit to setting below

observed temperature. Burner should stop.

c. Adjust limit to setting above observed

temperature. Burner should start.

d. Adjust thermostat to lowest setting. Adjust limit

to desired setting.

4. CHECK LOW WATER CUTOFF (if so equipped).

a. Adjust thermostat to highest setting.
b. With boiler operating, open drain valve and

slowly drain boiler.

c. Burner should stop when water level drops

below low water cutoff probe. Verify limit,

thermostat or other controls have not shut off

boiler.

d. Adjust thermostat to lowest setting. Refill boiler.

H.

Boiler is now ready to be put into service.

IMPORTANT

IF, DURING NORMAL OPERATION, IT IS

NECESSARY TO ADD WATER MORE FREQUENTLY

THAN ONCE A MONTH, CONSULT A QUALIFIED

SERVICE TECHNICIAN TO CHECK YOUR

SYSTEM FOR LEAKS.

A leaky system will increase the volume of make-up

water supplied to the boiler which can significantly

shorten the life of the boiler. Entrained in make-up

water are dissolved minerals and oxygen. When the

fresh, cool make-up water is heated in the boiler

the minerals fall out as sediment and the oxygen

escapes as a gas. Both can result in reduced boiler

life. The accumulation of sediment can eventually

isolate the water from contacting the steel. When this

happens the steel in that area gets extremely hot and

eventually cracks. The presence of free oxygen in the

boiler creates a corrosive atmosphere which, if the

concentration becomes high enough, can corrode the