beautypg.com

Iv. venting / air intake piping, Warning – Burnham 81433101R16-1/10 User Manual

Page 12

background image

1

IV. Venting / Air Intake Piping

A.

General Guidelines

1. Vent system installation must be in accordance

with these instructions and applicable provisions of

local building codes. Contact local building or fire

officials about restrictions and installation inspection

in your area.

2. The LE

®

DV Series is designed as a Direct Vent

boiler. In this configuration, all air for combustion

is supplied directly to the burner from outdoors and

flue gases are vented directly outdoors (through

wall). See Figures 10 and 11. The LEDV may

be side-wall vented with combustion air supplied

from indoors. This configuration may be used in

installations where infiltration provides adequate air

for combustion and ventilation. Flue gases are still

vented directly outdoors (through wall).

3. For minimum clearances to combustible materials

refer to Figure 2.

4. Maximum wall thickness that vent terminal may be

installed through is 10 inches.

WARNING

DO NOT locate vent terminal where exposed to

prevailing wind. Moisture and ice may form on

surfaces around vent termination. To prevent

deterioration, surfaces should be in good repair

(sealed, painted, etc.).

5. Locate the vent terminal so vent pipe is short and

direct, and at a place on the exterior wall that

complies with the minimum distances as specified in

Figure 8 and listed below. The vent terminal must

be located:
a. Not less than 12 inches above grade plus snow

accumulation (as measured to the nearest edge of

terminal).

b. Not less than 3 feet to center of terminal above

any forced air inlet located within 10 feet.

c. Not less than 1 foot to center of terminal

horizontally from any door, window or gravity

air inlet.

d. Not less than 7 feet to center of terminal above a

public walkway.

e. Not less than 3 feet to center of terminal from an

inside corner of an L-shaped structure.

f. Not less than 1 foot from nearest surface of

terminal to a roof soffit.

g. Not directly above, or not less than 6 feet

horizontally from an oil tank vent or gas meter.

h. Not less than 2 feet from nearest surface of

terminal to an adjacent building.

Figure 8: Vent Terminal Location