6. Inspect the transformer cables and connectors.
7. Remove and clean the cad cell.
8. Clean the blower wheel and the air control of any

lint.

9. Check all wiring for secure connections or insulation

breaks.

10. Re-adjust the burner as detailed in Section VII:

System Start-up, Paragraph F.

E.

Controls. Test Controls for proper operation as

detailed in Section VII: System Start-up, Paragraph G.

F.

Low water cutoff

(if so equipped).

1. Float Type

a. Monthly Blowoff. During the heating season, if

an external float type low water cutoff is on the

boiler, the blow off valve should be opened once

a month (use greater frequency where conditions

warrant), to flush out the sediment chamber so

the device will be free to function properly.

b. Annual Service. Float type low water cutoffs

should be dismantled annually by qualified

personnel, to the extent necessary to insure

freedom from obstructions and proper

functioning of the working parts. Inspect

connecting lines to boiler for accumulation of

mud, scale, etc., and clean as required. Examine

all visible wiring for brittle or worn insulation

and make sure electrical contacts are clean

and that they function properly. Give special

attention to solder joints on bellows and float

when this type of control is used. Check float

for evidence of collapse and check mercury bulb

(where applicable) for mercury separation or

discoloration.

2. Probe Type (Annual Service). Probe type LWCO

should be removed once a year, examined and

cleaned of any dirt accumulations to assure proper

operations. Do not attempt to repair mechanisms

in the field. Complete replacement mechanisms,

including necessary gaskets and installation

instructions, are available from the manufacturer.