Table 2B — Physical Data — 569J*16-25D/E Units — 60 Hz SI
UNIT SIZE 569J
*12D/E
*14D/E
NOMINAL CAPACITY (kW)
35.1
44
OPERATING WEIGHTS (kg)
NOVATION™ Coil (Al Tube)
226
229
Round Tube/Plate Fin Coil (Cu/Al Tube)
234
297
REFRIGERANT TYPE
‡
R-410A
NOVATION Operating Charge A/B, Typical (kg)
†
3.4 / 3.3
4.8 / 4.9
NOVATION Shipping Charge A/B (kg)
1.3 / 1.3
1.5 / 1.5
RTPF Operating Charge A/B, Typical (kg)
†
5.0 / 5.0
10.4 / 10.4
RTPF Shipping Charge A/B (kg)
3.6 / 3.6
7.7 / 7.7
COMPRESSOR
Qty...Type
2...Scroll
2...Scroll
Oil Charge A/B (L)
1.2
1.7
CONDENSER FANS
Qty...r/s
2...1100
Motor Hp NEMA
1
/
4
Diameter (mm)
560
Nominal Airflow (Cfm Total)
6000
Watts (Total)
610
RTPF CONDENSER COIL
Material (Tube/Fin)
Cu / Al
Coil Type
3
/
8
---in RTPF
Rows/Fins per Meter (Fins/m)
2 / 670
3 / 670
Face Area (sq m total)
2.3
3.0
NOVATION CONDENSER COIL
Material (Tube/Fin)
Al / Al
Coil Type
Novation
Rows/Fins per Meter (Fins/m)
1 / 670
Face Area (sq m total)
2.3
3.0
CONTROLS
Pressurestat Settings (kPa)
High Cutout
4347 ± 70
Cut-in
3482 ± 138
Low Cutout
372 ± 21
Cut-in
807 ± 34
PIPING CONNECTIONS (in. ODS)
Qty...Suction A/B
1...1
1
/
8
/ 1...1
1
/
8
1...1
3
/
8
/ 1...1
3
/
8
Qty...Liquid A/B
1...
3
/
8
/ 1...
3
/
8
1...
1
/
2
/ 1...
1
/
2
LEGEND
RTPF — Round Tube/Plate Fin
NEMA — National Electrical Manufacturers Association
ODS — Outside Diameter Sweat (socket)
‡
Unit is factory-supplied with partial charge only.
†
Typical operating charge with 7.62 m of interconnecting piping.
569J