beautypg.com

Warning – Bryant 569J User Manual

Page 16

background image

16

Solenoid drop control wiring: control the power to the

liquid line solenoid through a Solenoid Valve Relay (SVR)

in all units. Use part number HN61PC005 (field--supplied,

installed). 569J***A/B unit requires one SVR; 569J***D/E

unit requires two relays.

569J***D/E unit also requires a separate control power

transformer for the liquid solenoid valve loads. Select

transformer part number according to unit power supply.

Unit Power

Transformer Part #

208/230

HT01BD202

460

HT01BD702

575

HT01BD902

Mount the SVR (and transformer TRAN3 when used) in

unit control box. Connect per wiring schematic label on

unit or per Fig. 33 (569J***A/B) or Fig. 34 (569J***D/E).

Capacity Control Liquid Line Solenoid Valve:

Evaporator capacity staging control via direct thermostat

control of a liquid solenoid valve on the evaporator’s

second stage circuit is not possible with 569J models. If

this installation is a retrofit for a unit that included

automatic pressure--operated unloading, check the existing

thermostat and liquid solenoid valve wiring for possible

direct thermostat control of a solenoid valve; re--wire per

Figs. 16 or 17 and 33 or 34.

Selecting an Accumulator –

Because all 569J models use scroll compressors, an

accumulator is not required. If an accumulator is to be

added, check the accumulator manufacturer’s literature

carefully for indication of its suitability for use with

R--410A; look for minimum working pressure of 200 psig

(1380 kPa). Select the accumulator first on the basis of its

cataloged minimum capacity (tons) to ensure oil return from

the accumulator, then on tube size or holding capacity.

Make Piping Connections —

Piping connections at the 569J unit are ball valves with

stub tube extensions. Do not open the unit service valves

until all interconnecting tube brazing has been completed.

The stub tube connections include

1

/

4

-in SAE service

fittings with Schrader valve cores (see Fig. 9). Before

making any brazed connections to the unit service valves,

remove both Schrader valve caps and cores and save for

re-installation. Connect a source for nitrogen to one of

these service fittings during tube brazing to prevent the

formation of copper oxides inside the tubes at brazed

joints.

When connecting the field tubing to the 569J service

valves, wrap the valves in wet rags to prevent overheating

Pressure-test all joints from outdoor unit connections over

to the evaporator coil, using nitrogen as pressure and with

soap-and-bubbles.

When pressure-testing is completed, remove the nitrogen

source at the outdoor unit service valves and re-install the

two Schrader valve cores. Torque the cores to 2-3 in-lbs

(23-34 N-cm).

Factory
High-Flow
Access Port

Service Valve
with Stem Cap

Field Service
Access Port
(Schrader core)

Sweat
Connection

C10203

Fig. 9 -- Typical Piping Connection Assembly

Evacuation/Dehydration —

Evacuate and dehydrate the connected refrigeration

system(s) (excluding the 569J unit) to 500 microns using a

two-stage vacuum pump attached to the service ports

outside the 569J service valves, following description in

GTAC II, Module 4, System Dehydration.

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal

injury, death and/or equipment damage.
Puron

R

(R--410A) refrigerant systems operate at

higher pressure than standard R--22 systems. Do not

use R--22 service equipment or components on Puron

refrigerant equipment.

!

WARNING

This unit is designed for use with Puron (R--410A)

refrigerant. Do not use any other refrigerant in this

system.

Puron (R--410A) refrigerant is provided in pink (rose)

colored cylinders. These cylinders are available with and

without dip tubes; cylinders with dip tubes will have a

label indicating this feature. For a cylinder with a dip

tube, place the cylinder in the upright position (access

valve at the top) when removing liquid refrigerant for

charging. For a cylinder without a dip tube, invert the

cylinder (access valve on the bottom) when removing

liquid refrigerant.

Because Puron (R--410A) refrigerant is a blend, it is

strongly recommended that refrigerant always be removed

from the cylinder as a liquid. Admit liquid refrigerant into

the system in the discharge line. If adding refrigerant into

the suction line, use a commercial metering/expansion

device at the gauge manifold; remove liquid from the

cylinder, pass it through the metering device at the gauge

set and then pass it into the suction line as a vapor. Do not

remove Puron (R--410A) refrigerant from the cylinder as a

vapor.

569J