unit disconnect switch or HACR switch is open. Other

connection methods will result in the convenience outlet

circuit being de-energized when the unit disconnect or

HACR switch is open. See Fig. 13.

C10206

UNIT

VOLTAGE

CONNECT

AS

PRIMARY

CONNECTIONS

TRANSFORMER

TERMINALS

208,

230

240

L1: RED + YEL

L2: BLU + GRA

H1 + H3

H2 + H4

460

480

L1: RED

Splice BLU +

YEL

L2: GRA

H1

H2 + H3

H4

575

600

L1: RED

L2: GRA

H1

H2

Fig. 13 -- Powered Convenience Outlet Wiring

The unit-powered convenience outlet has a 1000 VA rated

transformer. Maximum continuous current must not

exceed 8 Amps.

B

50HJ542739

Maximum Continuous use : 8 Amps 24/7

Convenience Outlet Utilization

NOTICE

C10207

Fig. 14 -- Convenience Outlet Utilization Notice Label

Test the GFCI receptacle by pressing the TEST button on

the face of the receptacle to trip and open the receptacle.

Check for proper grounding wires and power line phasing

if the GFCI receptacle does not trip as required. Press the

RESET button to clear the tripped condition.

Fuse on power type: The factory fuse is a Bussman

“Fusetron” T-15, non-renewable screw-in (Edison base)

type plug fuse.

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal

injury or death.
Using unit-mounted convenience outlets: Units with

unit-mounded convenience outlet circuits will often

require that two disconnects be opened to de-energize

all power to the unit. Treat all units as electrically

energized until the convenience outlet power is also

checked and de-energization is confirmed. Observe

National Electrical Code Article 210, Branch Circuits,

for use of convenience outlets.

!

WARNING

Installing Weatherproof Cover: A weatherproof while in

use cover for the factory installed convenience outlets is

now required by UL standards. This cover cannot be

factory mounted due its depth; it must be installed at unit

installation. For shipment, the convenience outlet is

covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control

box. The kit includes the hinged cover, a backing plate

and gasket.

DISCONNECT

ALL

POWER

TO

UNIT

AND

CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet;

discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until

approximately

1

/

2--

in (13 mm) under screw heads are

exposed. Press the gasket over the screw heads. Slip the

backing plate over the screw heads at the keyhole slots

and align with the gasket; tighten the two screws until

snug (do not overtighten).

Mount the weatherproof cover to the backing plate as

shown in Fig. 15. Remove two slot fillers in the bottom of

the cover to permit service tool cords to exit the cover.

Check for full closing and latching.

C09022

Fig. 15 -- Weatherproof Cover Installation

569J