beautypg.com

Caution, Installation – Bryant 569J User Manual

Page 10

background image

10

.

INSTALLATION

Jobsite Survey

Complete the following checks before installation.

1. Consult local building codes and the NEC (National

Electrical Code) ANSI/NFPA 70 for special installa-

tion requirements.

2. Determine unit location (from project plans) or select

unit location.

3. Check for possible overhead obstructions which may

interfere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (pad,

rails or other) that provides for the minimum clearances

required for safety. This includes the clearance to

combustible surfaces, unit performance and service access

below, around and above unit as specified in unit

drawings. See Fig. 4.
NOTE: Local codes may require different clearances
than specified in Fig. 4. It is the responsibility of installers

to be knowledgeable in local codes and to modify the
recommended clearances to satisfy local codes.
NOTE: Consider also the effect of adjacent units on
airflow performance and control box safety clearance.
Do not install the outdoor unit in an area where fresh air

supply to the outdoor coil may be restricted or when

recirculation from the condenser fan discharge is possible.

Do not locate the unit in a well or next to high walls.

Evaluate the path and required line length for

interconnecting refrigeration piping, including suction

riser requirements (outdoor unit above indoor unit), liquid

line lift (outdoor unit below indoor unit) and hot gas

bypass line. Relocate sections to minimize the length of

interconnecting tubing.

DO NOT BURY REFRIGERATION LINES.

Although unit is weatherproof, avoid locations that permit

water from higher level runoff and overhangs to fall onto

the unit.

REAR:
Min 18” (457 mm)
requried for service

Note: Observe requirements for 39” (914 mm) operating clearance

on either Left or Rear coil opening.

RIGHT:
Min 18” (457 mm)
requried for service

LEFT:
Min 18” (457 mm)
requried for service

FRONT:
42” (1067 mm)

C110201

Fig. 4 -- Service Clearance Dimensional Drawing

Step 2 — Complete Pre-Installation Checks

Check Unit Electrical Characteristics: Confirm before

installation of unit that voltage, amperage and circuit

protection requirements listed on unit data plate agree with

power supply provided.

Un--crate Unit: Remove unit packaging except for the top

skid assembly, which should be left in place until after the

unit is rigged into its final location.

Inspect Shipment: File a claim with shipping company if

the shipment is damaged or incomplete.

Consider System Requirements:

S

Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.

S

Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and servicing unit. See Fig. NO TAG
for unit dimensions and weight distribution data.

S

Locate the unit so that the outdoor coil (condenser)
airflow is unrestricted on all sides and above.

S

The unit may be mounted on a level pad directly on the
base channels or mounted on raised pads at support
points. See Tables 1A through 2B for unit operating
weights. See Fig. 1 for weight distribution based on
recommended support points.

NOTE: If vibration isolators are required for a particular
installation, use the data in Fig. NO TAG to make the
proper selection.

Step 3 — Prepare Unit Mounting Support

Slab Mount —

Provide a level concrete slab that extends a minimum of 6

in. (150 mm) beyond unit cabinet. Install a gravel apron in

front of condenser coil air inlet to prevent grass and

foliage from obstructing airflow.

Step 4 — Rig and Mount the Unit

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage.
All panels must be in place when rigging. Unit is not

designed for handling by fork truck.

CAUTION

!

Rigging: These units are designed for overhead rigging.

Refer to the rigging label for preferred rigging method.

Spreader bars are not required if top crating is left on the

unit. All panels must be in place when rigging. As further

protection for coil faces, plywood sheets may be placed

against the sides of the unit, behind cables. Run cables to

a central suspension point so that the angle from the

horizontal is not less than 45 degrees. Raise and set the

unit down carefully.

569J