D1260/D1260B | Owner's Manual | Part III: Advanced Commands - DISPLAY REV ? (COMMAND + 5 + 9)

62

Bosch Security Systems | 9/04 | 50410D

5.

As you fault each point, your command center will
display the point text for 60 seconds and ring the
fire sounders for 2 seconds. This verifies that the
detection device is working properly. Your system
automatically resets smoke detectors.

When a resettable point (such as a smoke
detector) is faulted, the display shows

Sensors…resetting…please wait…

for 5

seconds. During this time power is removed
from smoke power relays.

Faulting a point more than once does not
increment the test count. However, the
command center emits a brief tone and
displays the point text each time you fault the
point allowing you to test multiple devices
assigned to one point.

6.

When the point has been tested, the display
changes to show

SMOKE DETECTOR tested.

7.

During the Fire Test you may want to see the
points that remain untested by pressing the

View

untested pts>

soft key.

The display shows ### pts untested.

Press the

Point information>

soft key to see

information about specific points that have not yet
been tested.
The display changes to show the information for
that point.

Move through this list by pressing the

Next

Point>

soft key.

Press the

soft key to return to the

###

points remain to be tested.

before continuing the

Fire Test.

8.

When all 24-hour points have been tested,

0

points remain to be tested

is displayed.

Press the

soft key.

The display momentarily shows

All points have

been tested.

before returning to idle text.

DISPLAY REV ? (COMMAND + 5 + 9)

1.

Ensure your keypad shows idle disarmed text.