12 4 3 x y – Bryant 582A User Manual
Page 6
provisions of local building code. In Canada, follow sections 7.2,
7.3, or 7.4 or Can/CGA. (Canadian Gas Association) B149
Installation Codes or applicable provisions of local building code.
Fig. 5—582A and 583A Unit Corner Weights
CORNER #
582A
583A
018
024
030
036
042
048
060
024
030
036
042
048
060
1
47.3
53.2
53.2
59.7
67.5
78.9
85.5
55.1
59.5
61.0
72.6
80.0
88.9
2
44.8
50.4
50.4
56.5
63.9
74.7
81.0
52.2
56.3
57.8
68.8
75.8
84.2
3
77.2
86.8
86.8
97.3
110.1
128.7
139.5
89.9
97.0
99.5
118.4
130.5
145.1
4
79.7
89.6
89.6
106.5
113.6
132.8
144.0
92.8
100.2
102.7
122.2
134.7
149.8
TOTAL WEIGHT
249
280
280
320
355
415
450
290
313
321
382
421
468
C00070
1
2
4
3
x
y
Fig. 6—Slab Mounting Details
C99014
OPTIONAL
RETURN
AIR
OPENING
OPTIONAL
SUPPLY
AIR
OPENING
EVAP.
COIL
COND.
COIL
2"
(50.8mm)
Fig. 7A—Threading Bolt for Rigging
C99067
HANDHOLD
FEED
HOOK
Fig. 7B—Suggested Rigging
SIZE
MAXIMUM WEIGHT
A
B
lb
kg
in.
mm
in.
mm
UNIT 582A
018
271
123.2
20.0
508.0
14.0
355.6
024
302
137.3
22.5
571.5
13.0
330.2
030
302
137.3
21.5
546.1
13.75
349.3
036
342
155.1
22.5
571.5
14.0
355.6
042
377
171.4
21.5
546.1
13.5
342.9
048
437
198.6
22.0
558.5
17.0
432.0
060
472
214.5
22.0
558.5
17.0
432.0
UNIT 583A
024
312
142
22.0
558.5
14.50
368.3
030
335
152
22.0
558.5
15.30
388.6
036
343
156
22.0
558.5
15.30
388.6
042
404
183
23.0
584.2
16.3
414.0
048
443
201
21.5
546.1
16.3
414.0
060
490
222
23.5
596.9
16.3
414.3
C99015
A
1226.3
(48.28”)
914-1371
(36”-54”)
927.57
(36”-52”)
PLACE RIGGING STRAPS IN
BASEPAN SLOT (BELOW RIGGING HOLDS)
BEFORE RIGGING
SEAL STRIP MUST BE IN
PLACE BEFORE PLACING
UNIT ON ROOF CURB
DUCTS
B