TABLE 16—TROUBLESHOOTING GUIDE—COOLING
SYMPTOM
CAUSE
REMEDY
Compressor and condenser fan
will not start.
Power Failure
Call power company.
Fuse blown or circuit breaker tripped
Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or control relay
Replace component.
Insufficient line voltage
Determine cause and correct.
Incorrect or faulty wiring
Check wiring diagram and rewire correctly.
Thermostat setting too high
Lower thermostat setting below room temperature.
Compressor will not
start but condenser
fan runs.
Faulty wiring or loose connections in compressor circuit
Check wiring and repair or replace.
Compressor motor burned out, seized, or internal
overload open
Determine cause
Replace compressor.
Defective run/start capacitor, overload, start relay
Determine cause and replace.
One leg of 3-phase power dead
Replace fuse or reset circuit breaker.
Determine cause.
Three-phase scroll compressor
(582A048 and 583A030-060 only)
makes excessive noise, and there may
be a low pressure differential.
Scroll compressor is rotating in the wrong direction
Correct the direction of rotation by reversing the
3-phase power leads to the unit. Shut down unit
to allow pressures to equalize.
Compressor cycles (other than
normally satisfying thermostat).
Refrigerant overcharge or undercharge
Recover refrigerant, evacuate system, and recharge to
capacities shown on nameplate.
Defective compressor
Replace and determine cause.
Insufficient line voltage
Determine cause and correct.
Blocked condenser
Determine cause and correct.
Defective run/start capacitor, overload or start relay
Determine cause and replace.
Defective thermostat
Replace thermostat.
Faulty condenser-fan motor or capacitor
Replace.
Restriction in refrigerant system
Locate restriction and remove.
Compressor operates continuously.
Dirty air filter
Replace filter.
Unit undersized for load
Decrease load or increase unit size.
Thermostat set too low
Reset thermostat.
Low refrigerant charge
Locate leak, repair, and recharge.
Leaking valves in compressor
Replace compressor.
Air in system
Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted
Clean coil or remove restriction .
Excessive head pressure.
Dirty air filter
Replace filter.
Dirty condenser coil
Clean coil.
Refrigerant overcharged
Recover excess refrigerant.
Air in system
Recover refrigerant, evacuate system, and recharge.
Condenser air restricted or air short-cycling
Determine cause and correct.
Head pressure too low.
Low refrigerant charge
Check for leaks, repair, and recharge.
Compressor valves leaking
Replace compressor.
Restriction in liquid tube
Remove restriction.
Excessive suction pressure.
High heat load
Check for source and eliminate.
Compressor valves leaking
Replace compressor.
Refrigerant overcharged
Recover excess refrigerant.
Suction pressure too low.
Dirty air filter
Replace Filter.
Low refrigerant charge
Check for leaks, repair, and recharge.
Metering device or low side restricted
Remove source of restriction.
Insufficient evaporator airflow
Increase air quantity. Check filter — replace if necessary.
Temperature too low in conditioned area
Reset thermostat.
Outdoor ambient below 40°F
Install low-ambient kit .
Field-installed filter-drier restricted
Replace.