TABLE 17—TROUBLESHOOTING GUIDE–HEATING
SYMPTOM
CAUSE
REMEDY
Burners will not ignite.
Water in gas line
Drain. Install drip leg.
No power to furnace
Check power supply fuses, wiring, or circuit breaker.
No 24-v power supply to control circuit
Check transformer.
NOTE: Some transformers have internal overcurrent
protection that requires a cool-down period to reset.
Miswired or loose connections
Check all wiring and wirenut connections
Burned-out heat anticipator in
thermostat
Replace thermostat.
Broken thermostat wire
Run continuity check. Replace wire if necessary.
Misaligned spark electrodes
Check flame ignition and sense electrode positioning.
Adjust as necessary.
No gas at main burners
1.Check gas line for air. Purge as necessary.
NOTE: After purging gas line of air, wait at least 5 minutes for any
gas to dissipate before attempting to light unit.
2. Check gas valve.
Inadequate heating.
Dirty air filter
Clean or replace filter as necessary.
Gas input to furnace too low
Check gas pressure at manifold match with that on
unit nameplate.
Unit undersized for application
Replace with proper unit or add additional unit.
Restricted airflow
Clean or replace filter. Remove any restriction.
Blower speed too low
Use faster speed tap if available, or install alternate
motor.
Limit switch cycles main burners
Check rotation of blower, thermostat heat anticipator settings,
temperature rise of unit. Adjust as necessary.
Poor flame characteristics.
Incomplete combustion results in:
Aldehyde odors, carbon monoxide, sooting
flame, floating flame
1.Tighten all screws around burner compartment.
2. Cracked heat exchanger. Replace.
3. Unit overfired. Reduce input (change orifices or
adjust gas line or manifold pressure).
4. Check burner alignment.