openings. Installation of flexible duct connector is recommended
to prevent transmission of vibration and /or noise to structure. All
ductwork should be secured to the flanges. Insulate and weather-
proof all external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabinet
return-air static shall not exceed -.25 in. wg.
IV.
PROVIDE CLEARANCES
The required minimum operating and service clearances are shown
in Fig. 2 and 3. Adequate combustion, ventilation and condenser
air must be provided in accordance with section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code ANSI
(American National Standards Institute) Z223.1 or applicable
Fig. 4—Roof Curb Dimensions
UNIT SIZE
ODS CATALOG NUMBER
A
IN. (MM)
B
IN. (MM)
C
IN. (MM)
D
IN. (MM)
582A018-042
583A024-036
CPRFCURB006A00
8 (203)
11(279)
161/2 (419)
28-3/4 (730)
CPRFCURB007A00
14 (356)
11(279)
161/2 (419)
28-3/4 (730)
582A048-060
583A042-060
CPRFCURB008A00
8 (203)
16 3/16 (411)
17 3/8 (441)
40-1/4 (1022)
CPRFCURB009A00
14 (356)
16 3/16 (411)
17 3/8 (441)
40-1/4 (1022)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 lb density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic
conditions. This bracket is available through Micrometl.
C00076
Gasket around
outer edge
Insulated
deck pan
Gasket around
duct
S/A
R/A
HVAC unit
base
*Gasketing
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant strip
field supplied
*Provided with roofcurb
Roof
Duct work
field supplied
Insulation (field
supplied)
Roofcurb*
Wood nailer*
Gasketing
inner flange*
Screw
(NOTE A)
Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
HVAC unit
base
*Gasketing
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant strip
field supplied
*Provided with roofcurb
Roof
Duct work
field supplied
Insulation (field
supplied)
Roofcurb*
Wood nailer*
Gasketing
inner flange*
Screw
(NOTE A)
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
A
B Typ.
Supply opening
(B x C)
Long
Support
D
44
5
/
16
"
(1125.5mm)
Return opening
(B X C)
Insulated
deck pan
Short
Support
C Typ.
—5—
→