WARNING:
The ability to properly perform mainte-
nance on this equipment requires certain expertise, me-
chanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the User’s Manual. FAILURE TO HEED
THIS WARNING COULD RESULT IN SERIOUS IN-
JURY AND POSSIBLE DAMAGE TO THIS EQUIP-
MENT.
WARNING:
Failure to follow these warnings could
result in serious injury:
1. First, turn off gas supply to the unit. Then turn off
electrical power to the unit and install lockout tag
before performing any maintenance or service on the
unit.
2. Use extreme caution when removing panels and parts.
As with any mechanical equipment, personal injury
can result from sharp edges, etc.
3. Never place anything combustible either on, or in
contact with, the unit.
4. Should overheating occur or the gas supply fail to shut
off, turn off external main manual gas valve to the unit.
Then shut off electrical supply and install lockout tag.
TABLE 13—DRY COIL AIR DELIVERY* – HORIZONTAL AND DOWNFLOW DISCHARGE –
UNIT 583A024-060 (DEDUCT 10 PERCENT FOR 208 VOLTS)
230 AND 460 VOLT
Unit
Motor
Speed
External Static Pressure (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
024
Low
Watts
281
282
281
278
276
—
—
—
—
—
—
Cfm
899
828
757
691
619
—
—
—
—
—
—
Med
Watts
—
—
—
375
370
363
357
352
—
—
—
Cfm
—
—
—
969
897
824
744
649
—
—
—
High
Watts
—
—
—
—
—
468
457
444
431
423
—
Cfm
—
—
—
—
—
994
913
826
730
620
—
030
Low
Watts
246
244
243
241
—
—
—
—
—
—
—
Cfm
982
860
808
736
—
—
—
—
—
—
—
Med
Watts
343
339
336
332
328
322
317
—
—
—
—
Cfm
1233
1170
1109
1038
953
855
754
—
—
—
—
High
Watts
—
—
—
—
441
432
421
410
400
—
—
Cfm
—
—
—
—
1202
1111
1021
929
826
—
—
036
Low
Watts
—
470
458
445
430
415
399
384
—
—
—
Cfm
—
1463
1406
1344
1273
1188
1091
983
—
—
—
Med
Watts
—
—
514
501
487
471
455
438
422
—
—
Cfm
—
—
1497
1428
1348
1255
1152
1042
929
—
—
High
Watts
—
—
—
646
636
626
614
602
589
—
—
Cfm
—
—
—
1491
1412
1325
1228
1120
1003
—
—
042
Low
Watts
643
625
614
605
593
574
549
518
485
454
—
Cfm
1626
1614
1579
1532
1478
1421
1361
1295
1218
1120
—
Med
Watts
—
—
—
—
726
695
661
625
591
561
540
Cfm
—
—
—
—
1731
1672
1610
1541
1456
1345
1193
High
Watts
—
—
—
—
—
—
—
790
766
742
713
Cfm
—
—
—
—
—
—
—
1699
1602
1494
1367
048
Low
Watts
614
588
577
572
566
556
539
517
491
—
—
Cfm
1591
1549
1518
1490
1460
1421
1372
1312
1242
—
—
Med
Watts
778
756
738
719
699
676
650
623
596
572
555
Cfm
1854
1837
1804
1759
1705
1643
1577
1508
1440
1375
1315
High
Watts
—
—
—
—
896
862
829
800
775
752
728
Cfm
—
—
—
—
1956
1879
1797
1709
1615
1514
1406
060
Low
Watts
834
813
782
746
712
680
652
626
—
—
—
Cfm
2016
1955
1898
1840
1781
1717
1646
1566
—
—
—
Med
Watts
941
889
851
822
797
772
745
714
679
639
—
Cfm
2379
2233
2124
2038
1964
1892
1814
1727
1626
1511
—
High
Watts
—
—
960
949
920
883
845
812
783
753
—
Cfm
—
—
2497
2224
2075
1986
1915
1831
1721
1588
—
* Air delivery values are without air filter and are for dry coil (See Table 15–583A Wet Coil Pressure Drop table).
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
—23—